beautypg.com

Schwank sportSchwank User Manual

Page 12

background image

sportSchwank Manual

IM080731

RD: July 2008

RL: 01A

BA

Page 9

TABLE 3: MINIMUM CLEARANCES TO COMBUSTIBLE

7. MINIMUM CLEARANCES TO COMBUSTIBLES

The structure, materials, or items in proximity to, or stored under the

heater will be subjected to radiant heat and could be seriously damaged.
The clearances to combustible material represent the minimum dis-
tances that must be maintained between the outer heater surface and a
nearby surface so that a surface temperature of 90F°(50C°) above ambi-
ent is not exceeded.

It is the installer’s responsibility to ensure that building materials with a

low heat tolerance which may degrade at lower temperatures are pro-
tected to prevent degradation.

sportSchwank

Angle Mounted 1° to 30°

Horizontal

ABOVE

A

In. [cm]

REAR

R

In. [cm]

BELOW

B

In. [cm]

FRONT

F

In. [cm]

TOP

T

In. [cm]

SIDES

S

In. [cm]

UNDER

U

In. [cm]

10

24" [61] 8" [20] 66" [91] 66" [170] 18" [46] 30" [76]

90" [229]

15

24" [61] 8" [20] 66" [91] 66" [168] 18" [46] 30" [76]

96" [244]

20

24" [61] 8" [20] 70" [91] 70" [178] 18" [46] 36" [91] 100" [254]

30

24" [61] 8" [20] 74" [91] 74" [188] 18" [46] 42" [107] 105" [267]

FIGURE 4: MINIMUM CLEARANCES TO COMBUSTIBLE

R

A

F

B

T

S

U

S

Horizontal

Angle Mounted
1° to 30°