17. TROUBLESHOOTING GUIDE
SET THERMOSTAT TO CALL FOR HEAT
IS THE HEATER BURNING?
THE SYSTEM IS WORKING PROPERLY. 
STOP. 
YES
NO
IS THERE LINE VOLTAGE (120V) OR 
24 VOLTS TO THE THERMOSTAT 
CONTROL? 
→CHECK CIRCUIT BREAKERS OR FUSE 
→CHECK ON/OFF SWITCH 
→CHECK NIGHT TIME SET BACK CONTROL 
→CHECK FOR PROPER GAUGE OF WIRE 
→(24V) CHECK CONTROL CENTER TRANS-
FORMER. REPLACE IF NECESSARY
NO
IS THERE VOLTAGE (120V) 
TO THE FAN SYSTEM? 
YES
YES
→CHECK ELECTRICAL CONNECTION 
 FROM THERMOSTAT TO FAN MOTOR 
→CHECK THERMOSTAT, REPLACE IF 
 NECESSARY 
NO
IS FAN MOTOR OPERATING?
→CHECK EXHAUST FAN MOTOR, REPLACE 
 IF 
NECESSARY
NO
IS THERE 120 VOLTS TO 
THE TRANSFORMER? 
YES
YES
NO
CONT’D
→CHECK FOR DARK SPOTS OR LINES ON 
THE TILE SURFACE 
→’DARK’ AREAS REPRESENT CRACKS OR 
BLOCKAGE OF THE TILE 
→SEE ’SERVICE’ SECTION 15 
→CHECK ELECTRICAL CONNECTION FROM AIR 
 SWITCH TO TRANSFORMER. 
→ENSURE AIR SWITCH IS INSTALLED PROPERLY 
→ENSURE AIR HOSE IS CONNECTED PROPERLY
 FROM AIR SWITCH TO EXHAUST FAN 
→CHECK AIR SWITCH, REPLACE IF NECESSARY 
IS THERE 120 VOLTS TO 
THE AIR PROVING SWITCH? 
→CHECK ELECTRICALCONNECTION 
 TO AIR PROVING SWITCH 
YES
NO