Calibration frequency – RKI Instruments 65-2451RK User Manual
Page 16

12 • 65-2451RK Hydrogen Transmitter
NOTE:
When a transmitter is first powered up with a new amplifier, the initial output
may be either high or below zero depending on the setting of the zero pot. Be
sure to make arrangements so that this does not cause unwanted alarms.
9.
Turn on power to the controller.
10. Turn on the controller and place it into normal operation.
11. Allow the transmitter to warm-up for 5 minutes.
12. Calibrate the transmitter as described in “Calibration” on page 13 of this manual.
Calibration Frequency
Although there is no particular calibration frequency that is correct for all applications, a
calibration frequency of every 3 to 6 months is adequate for most hydrogen transmitter
applications. Unless experience in a particular application dictates otherwise, RKI
Instruments, Inc. recommends a calibration frequency of every 3 months.
If an application is not very demanding, for example detection in a clean, temperature
controlled environment where hydrogen is not normally present and calibration
adjustments are minimal at calibration, then a calibration frequency of every 6 months is
adequate.
If an application is very demanding, for example if hydrogen is present often and in
significant concentrations or the environment is not well controlled, then more frequent
calibration than every 3 months may be necessary. If potential catalyst poisons are known
or likely to be present, more frequent calibration than every 3 months will be necessary.
Table 5:Reconnecting the LEL
Detector to the Amplifier
Amplifier Detector
Terminal Strip
Detector Lead
DETECTOR “R”
RED
DETECTOR “W”
WHT
DETECTOR “G”
GREEN
DETECTOR “B”
BLK