Troubleshooting, Replacing the ir lel detector – RKI Instruments 61-0190RK User Manual
Page 11
61-1003RK/61-0190RK Combustible Gas Detector • 7
10. Unscrew the regulator from the calibration cylinder.
11. Unscrew the calibration cup from the detector.
12. When the display reading falls below the alarm setpoints, return the controller to
normal operation or enable external alarms.
13. Store the components of the calibration kit in a safe place.
Biannually
Calibrate the detector every six months as described in “Calibration” on page 8.
Troubleshooting
The troubleshooting guide describes symptoms, probable causes, and recommended
action for problems you may encounter with the combustible gas detector.
NOTE:
This troubleshooting guide describes detector problems only. See the controller
operator’s manual for problems you may encounter with the controller.
Replacing the IR LEL Detector
1.
Turn off the controller.
2.
Turn off power to the controller.
3.
Remove the junction box cover.
4.
Disconnect the detector leads from the terminal block inside the junction box. Note
the position of the color-coded leads as you remove them.
Table 2:Troubleshooting the Combustible Gas Detector
Condition
Symptom(s)
Probable Causes
Recommended Action
Fail Condition
• Controller indicates a
fail condition.
• The detector wiring is
disconnected or
misconnected.
• The detector zero
signal is low enough to
cause a fail condition.
• The detector is
malfunctioning.
1. Verify that the detector wiring is
correct and secure.
2. Calibrate the detector.
3. If the fail condition continues, replace
the detector.
4. If the fail condition continues, contact
RKI for further instruction.
Slow or No
Response/
Difficult or
Unable to
Calibrate
• Detector responds
slowly or does not
respond to response
test.
• Unable to accurately
set the zero or
response reading
during calibration.
• Detector requires
frequent calibration.
Note: Under “normal”
circumstances, the
detector requires
calibration once every
six months.
Some applications may
require a more frequent
calibration schedule.
• The calibration cylinder
is low, out-dated, or
defective.
• The detector is
malfunctioning.
1. Verify that the calibration cylinder
contains an adequate supply of a
fresh test sample.
2. If the calibration/response difficulties
continue, replace the detector.
3. If the calibration/response difficulties
continue, contact RKI for further
instruction.