Installation, Mounting the combustible gas detector – RKI Instruments 61-1000RKSS-05 User Manual
Page 7

61-1000RKSS-05 Combustible Gas Detector• 3
Installation
This section describes procedures to mount the combustible gas detector in the
monitoring environment and wire the detector to a controller.
Mounting the Combustible Gas Detector
1.
Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.
•
Select a site where the detector is not likely to be bumped or disturbed. Make sure
there is sufficient room to perform start-up, maintenance, and calibration
procedures.
•
Select a site where the target gas is likely to be found first. For lighter gases,
mount the detector near the ceiling; for heavier gases, mount the detector near the
floor.
Figure 2: Mounting the Combustible Gas Detector
2.
At the mounting site you select, hang or mount the junction box with the detector
facing down (see Figure 2).
2.40
3.15
3.66
.75
J-Box
Text Oriented
This Way
.20 Dia. x .45
Slot, 2X
3/4 NPT
Female,
2X