Model 1017-03 Operator’s Manual
• 11
3.
Allow the Model 1017-03 to draw sample for one minute.
4.
Follow the directions in the controller’s operator’s manual for setting the span.
5.
Disconnect the sample tubing from the inlet fitting.
6.
Unscrew the regulator from the combustible gas calibration cylinder.
Returning to Normal Operation
1.
Reconnect the incoming sample line.
2.
Wait approximately one minute to allow the combustible gas reading to stabilize.
3.
Follow the instructions in the controller’s operator’s manual to exit the calibration
mode.
4.
Store the components of the calibration kit in a safe and convenient place.
Parts List
Table 4 lists replacement parts and accessories for the Model 1017-03.
Table 2: Parts List
Part Number
Description
06-1200RK
Sample tubing, 4 x 6 mm, specify length (used for internal plumbing)
17-2593RK
Brass tubing insert for .25” O.D. x .17” I.D. flexible tubing (used when
flexible tubing is connected to inlet or exhaust fitting)
17-2673RK
Front ferrule (for inlet and exhaust fittings)
17-2678RK
Back ferrule (for inlet and exhaust fittings)
30-1016RK
Pump, w/cable and connector
33-3050RK
MC filter w/cartridge & flow monitor (recommended for installation
external to Model 1017-03 in inlet line)
81-0002RK-01
Calibration cylinder, 50% LEL hydrogen in air, 34 liter
81-0002RK-03
Calibration cylinder, 50% LEL hydrogen in air, 103 liter
81-0007RK-01
Calibration cylinder, 50% LEL hexane in air, 34 liter
81-0012RK-01
Calibration cylinder, 50% LEL methane in air, 34 liter
81-0012RK-03
Calibration cylinder, 50% LEL methane in air, 103 liter
81-0076RK-01
Zero air calibration cylinder, 34 liter
81-0076RK-03
Zero air calibration cylinder, 103 liter
81-1001RK
Dispensing valve (with knob)
81-1054RK
Regulator (demand flow)
81-1126RK
Gas collection bag (2 liter)
NC-6245
Combustible gas sensor, plug-in type, LEL