TO LIGHT UNIT

WARNING:

1. Do not turn off the electrical power to unit without first

turning off the gas supply.

2. Before attempting to start the gas heating section,

familiarize yourself with all the procedures that must
be followed.

If you do not follow these instructions exactly, a fire or
explosion may result, causing property damage, serious
injury, or death.

1. Set the temperature selector on room thermostat to the

lowest temperature setting and set system switch to HEAT.

2. Close the external manual shutoff valve.

3. Turn off the electrical supply to the unit.

4. Remove the front access panel with a 5/16 in. nut driver.

5. Move the selector switch on the internal gas valve to the

OFF position and wait 5 minutes.

6. Move the selector switch on the internal gas valve to the ON

position.

7. Replace the front access panel.

8. Turn on the electrical supply to unit.

9. Open the external manual shutoff valve.

10. Set the temperature selector on room thermostat slightly

above room temperature to start unit. The induced-draft
combustion-air fan will start. Main gas valve will open and
main burners should ignite within 5 seconds. If the burner
does not light within 5 seconds, the ignition module will go
into a RETRY mode after a period of approximately 22
seconds (following the 5-second ignition period).

If the burners do not light within 15 minutes of the initial
call for heat, there is a lockout.

11. Set the temperature selector on room thermostat to desired

setting.

WARNING:

1. If the main burners fail to light, or the blower fails to

start, shut down gas heating section and call your
dealer for service.

2. Never attempt to manually light the main burners on

unit with a match, lighter, or any other flame. If the
electric sparking device fails to light the main burners,
refer to the following shutdown procedures, then call
your dealer as soon as possible.

Failure to follow these requirements could result in
serious injury or death.

TO SHUT UNIT OFF

WARNING:

Do not turn off the electrical power to unit

without first turning off the gas supply.
Failure to follow these procedures can result in fire,
serious injury, or death.

1. Set the temperature selector on room thermostat to lowest

temperature setting and set system switch to OFF.

2. Close the external manual shutoff valve.

3. Turn off the electrical power supply to the unit.

4. Remove the front access panel.

5. Move the selector switch on the internal gas valve to the

OFF position.

6. Replace the burner access panel.

7. Restore electrical power to the unit and set system switch to

COOL to ensure operation of the cooling system during the
cooling season.

FRONT
ACCESS PANEL

NOTE:

If unit is being shut down because the heating season has

ended, make sure to turn on power to cooling system.

If unit is being shut down because of a malfunction, call your
dealer as soon as possible.

Should overheating occur or the gas supply fail to shut off, shut off
the manual gas valve to the unit before shutting off the electrical
supply.

Fig. 2—Gas Heating/Electric Cooling Unit

Front Access Panel

ROUTINE MAINTENANCE

All routine maintenance should be handled by skilled, experienced
personnel. Your dealer can help you establish a standard proce-
dure.

For your safety, keep the unit area clear and free of combustible
materials, gasoline, and other flammable liquids and vapors.

To assure proper functioning of the unit, flow of combustion and
ventilating air must not be obstructed from reaching the unit.
Clearance of at least 48 in. is required from top of unit and on sides
except the power entry side (42 in. clearance) and the duct side (12
in. minimum clearance).

MAINTENANCE AND CARE FOR THE EQUIPMENT

OWNER

Before proceeding with those things you might want to maintain
yourself, please carefully consider the following: