DCA-150SSVU— OPERATION AND PARTS MANUAL (STD)— REV. #1 (06/03/03) — PAGE 43
DCA-150SSVU — GENERATOR START-UP PROCEDURE (MANUAL)
Figure 59. Engine Tachometer
16. The tachometer (Figure 59) will indicate the speed of
the engine when the generator is operating. Under normal
operating conditions this speed is approximately 1800
RPM’s.
17. Turn the
main, GFCI, and aux. circuit breakers to the
“ON” position (Figure 60).
15. The coolant temperature gauge (Figure 58) will indicate
the coolant temperature. Under normal operating
conditions the coolant temperature is between 165 and
215 degrees fahrenheit.
Figure 58. Coolant Temperature Gauge
18. Observe the generator's ammeter (Figure 61) and verify
it reads the anticipated amount of current with respect
to the load. The ammeter will only display a current
reading if the load is in use.
19. The generator will run until manually stopped or an
abnormal condition occurs.
Figure 61. Ammeter (Load)
Figure 60. Main, AUX. and GFCI
Circuit Breakers (ON)
14. The engine oil pressure gauge (Figure 57) will indicate
the oil pressure (kg/ cm
2
)
of the engine. Under normal
operating conditions the oil pressure is approximately
Figure 57. Oil Pressure Gauge