beautypg.com

Bryan water-pak, Indirect water heater systems, Indirect heater specifications – Bryan Boilers CLM-120-WT-FDG-844-AV-CM-IN User Manual

Page 4: Water-pak selection, Selection procedure example, Storage tank specifications

background image

Bryan Water-Pak

TM

Indirect Water Heater Systems

Specifications subject to change without notice.
Contact factory to consult on other boiler options.

Form No. 2300 ©2004 Bryan Steam LLC

Printed in USA

54-5368

Indirect Heater Specifications

Heater

Model

Output

Series

Number

BTU/HR 80°-140° 60°-140° 40°-140° 40°-160°

DR SERIES

DR/F-350-WT

280,000

559

420

336

(Forced Draft)

DR/F-450-WT

360,000

720

540

432

F SERIES

DR/F-650-WT

520,000

1,039

780

624

(Atmospheric)

DR/F-850-WT

680,000

1,359

1,020

816

CLM SERIES

CLM-120-WT

960,000

1,920

1,440

1,152

960

(Forced Draft)

CLM-150-WT 1,200,000

2,400

1,800

1,440

1,200

&

CLM-180-WT 1,440,000

2,880

2,160

1,728

1,440

(Atmospheric)

CLM-210-WT 1,680,000

3,660

2,520

2,016

1,680

CLM-240-WT 1,920,000

3,840

2,880

2,304

1,920

CLM-270-WT 2,160,000

4,320

3,240

2,592

2,160

CLM-300-WT 2,400,000

4,800

3,600

2,880

2,400

K SERIES

K-350-WT

2,800,000

5,600

4,200

3,360

2,800

(Atmospheric)

K-400-WT

3,200,000

6,400

4,800

3,840

3,200

K-450-WT

3,600,000

7,200

5,400

4,320

3,600

K-500-WT †

4,000,000

8,000

6,000

4,800

4,000

K-550-WT †

4,400,000

8,800

6,600

5,280

4,400

K-600-WT †

4,800,000

9,600

7,200

5,760

4,800

K-650-WT †

5,200,000 10,400

7,800

6,240

5,200

AB SERIES

AB-90-WT

720,000

1,440

1,080

864

720

(Forced Draft)

AB-120-WT

960,000

1,920

1,440

1,152

960

AB-150-WT

1,200,000

2,400

1,800

1,440

1,200

AB-200-WT

1,680,000

3,360

2,520

2,016

1,680

AB-250-WT

2,000,000

4,000

3,000

2,400

1,999

AB-300-WT

2,400,000

4,800

3,600

2,880

2,400

RV SERIES

RV-350-WT

2,800,000

5,600

4,200

3,360

2,800

(Forced Draft)

RV-400-WT

3,200,000

6,400

4,800

3,840

3,200

RV-450-WT

3,600,000

7,200

5,400

4,320

3,600

RV-500-WT †

4,000,000

8,000

6,000

4,800

4,000

RV-550-WT †

4,400,000

8,800

6,600

4,280

4,400

RV-600-WT †

4,800,000

9,600

7,200

5,760

4,800

RV-700-WT †

5,600,000 11,200

8,400

6,720

5,600

RV-800-WT †

6,400,000 12,800

9,600

7,680

6,400

Bryan Steam LLC — Leaders Since 1916
783 N. Chili Ave., Peru, Indiana 46970 U.S.A.
Phone:765-473-6651 • Internet: www.bryanboilers.com
Fax: 765-473-3074 • E-mail: [email protected]

Water-Pak Selection

Water-Pak units are built to furnish a very wide selection of
recovery rates, storage capacities and configurations. Both
horizontal and vertical tanks are available to best fit into the
space allocation. In addition to the combinations of "settings"
shown below, other combinations, arrangements and sizes
are possible. Fuel selection includes gas (atmospheric or
forced draft), oil, gas-oil or electric (consult factory).

1. Select Heater Model based on "Heater Specifications" table

below.

2. Select storage capacity from "Storage Tank Specifications"

tables, horizontal or vertical tank depending on space
considerations.

3. Choose appropriate "Setting" from "Heater, Tank Setting"

diagrams on previous page.

Selection Procedure Example

A requirement of 800 gph at 100° rise. Storage capacity 1000
gallons. Fuel, gas. Tank lining, cement.

1. From "Heater Specifications" table, select Model No. CLM-

120-WT Gas, rated at 1,152 gph, 40° to 140° rise.

2. From the "Storage Tank Specifications" tables, suppose

you select the 1045 gallon horizontal tank.

3. Then the setting shown in diagram "AH" (horizontal tank)

would be appropriate.

Specify:

Specify:

Specify:

Specify:

Specify:
Water-Pak System CLM-120-WT - G - 1045 - AH - CM - IN

Storage Tank Specifications

Tank

Tank

Approximate

Capacity

Dia × Length

Weight

gallons

in (cm)

lbs (Kg)

Horizontal Tanks

H-387

36Ч96 (91.4Ч243.8)

2,000 (907)

H-520

42Ч96 (106.7Ч243.8)

2,200 (998)

H-802

42Ч144 (106.7Ч365.8)

3,000 (1,361)

H-1045

48Ч144 (121.9Ч365.8)

3,800 (1,724)

H-1546

54Ч168 (137.2Ч426.7)

5,600 (2,540)

H-2188

60Ч192 (152.4Ч487.7)

6,900 (3,130)

H-2699

72Ч168 (182.9Ч426.7)

8,100 (3,674)

H-3533

72Ч216 (182.9Ч548.6)

10,100 (4,581)

Vertical Tanks

V-335

36Ч84 (91.40Ч213.4)

1,700 (771)

V-520

42Ч96 (106.7Ч243.8)

2,200 (998)

V-665

48Ч96 (121.9Ч243.8)

2,700 (1,225)

V-844

54Ч96 (137.2Ч243.8)

3,100 (1,406)

V-1030

60Ч96 (152.4Ч243.8)

4,000 (1,814)

V-1447

72Ч96 (182.9Ч243.8)

5,300 (2,404)

V-1922

84Ч96 (213.4Ч243.8)

7,000 (3,175)

Fuel

Fuel

Fuel

Fuel

Fuel
G—gas
O—oil
GO—gas-oil

Storage

Storage

Storage

Storage

Storage
Section

Section

Section

Section

Section
Size

Size

Size

Size

Size
(gals.)

Tank

Tank

Tank

Tank

Tank
Insulated

Insulated

Insulated

Insulated

Insulated
PVC

PVC

PVC

PVC

PVC
Jacket

Jacket

Jacket

Jacket

Jacket

Indirect

Indirect

Indirect

Indirect

Indirect
Heater

Heater

Heater

Heater

Heater
Model

Model

Model

Model

Model

Setting

Setting

Setting

Setting

Setting

Tank Lining

Tank Lining

Tank Lining

Tank Lining

Tank Lining
CM—cement
PH—phenolic

Gallons Per Hour*

Heater Capacity

† These units are equipped with two heat exchangers as standard and require a copper header to be field supplied.

*

Note 1: Contact factory for ratings at other conditions.

Note 2: Heater is not intended to provide the temperature increases shown above instantly, but will raise the
temperature of the gallons listed to final storage temperature within one hour.

Note 3: Select adequate storage tank capacity to handle peak demand. Keep in mind that, typically, only 75%
of tank capacity is usable storage.