PHYSICAL DATA

Required filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling air-

flow or the heating airflow velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity type. Air filter pressure
drop for non-standard filters must not exceed 0.08 in. wg.

*

Based on altitude of 0 to 2000 ft.

UNIT SIZE 574B

024040

030040

030060

036060

036090

042060

042090

NOMINAL CAPACITY (ton)

2

2-1/2

2-1/2

3

3

3-1/2

3-1/2

OPERATING WEIGHT (lb)

350

388

388

COMPRESSORS

Scroll

Quantity

1

REFRIGERANT (R-410A)

Quantity (lb)

7.3

9.5

9.5

REFRIGERANT METERING DEVICE

Indoor

TXV

CONDENSER COIL

Rows—Fins/in.
Face Area (sq ft)

2/21

11.95

2/21
13.7

2/21
13.7

CONDENSER FAN

Nominal Cfm
Diameter (in.)
Motor Hp (Rpm)

2350

22

1/8 (825)

2350

22

1/8 (825)

2350

22

1/8 (825)

EVAPORATOR COIL

Rows—fins/in.
Face Area (sq ft)

3/15

3.7

4/15

3.7

4/15

3.7

EVAPORATOR BLOWER

Nominal Airflow (Cfm)
Size (in.)
Motor Hp (Rpm)

800

10 x 10

1/2

1150

11 x 10

3/4

1150

11 x 10

3/4

FURNACE SECTION*

Burner Orifice No. (Qty…Drill Size)

Natural

Burner Orifice No. (Qty…Drill Size)

Propane

2…44

2…50

2…38

2…46

3…38

3…46

HIGH-PRESSURE SWITCH (psig)

Cutout

Reset (Auto.)

610 ± 15
420 ± 25

LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

(Liquid Line) (psig)

Cutout

Reset (Auto.)

20 ± 5

45 ± 10

RETURN-AIR FILTERS (in.)†

Throwaway

20 x 24 x 1

20 x 24 x 1

20 x 24 x 1

20 x 24 x 1

20 x 24 x 1

24 x 30 x 1

24 x 30 x 1