Approvals information, Fusible links, Pressure/open fryers – BKI FH-28WM Ventless Hood System User Manual
Page 7: Sandwich grills

Ventless Hood System
Introduction
5
Approvals Information
Failure to adhere to building, fire and electrical codes during installation of this 
unit could result in death, serious injury or property damage. The authority having 
jurisdiction, such as the local building inspector or fire marshal, should be 
consulted prior to installation to insure compliance with applicable codes. 
 
In the event of an appliance fire, serious injury, property damage or death could 
occur if the appliance is powered from a source other than the hood. The cooking 
appliance used under this hood MUST receive its input power from the hood. 
Electricity is automatically removed from the hood and the appliance when the 
Fire Extinguishing System is activated. 
 
In the event of an appliance fire, serious injury, property damage or death could 
occur if the remote pull station is not properly installed. The remote pull is to be 
clearly marked, located in a path of exit or egress and must comply with 
applicable codes. 
 
It is the responsibility of the owner to verify that the cooking appliance is eligible 
for use with this hood. 
 
This filter hood is an ETL Listed ductless hood for use with Listed commercial 
cooking appliances only (griddle or fryer). 
Fusible Links
 Fusible links to be UL Listed, 165 F., load rating 3-45 lbs.
Pressure/Open Fryers
 Pressure fryers acceptable for use with this hood shall be constructed such that when the lid is
released or unlatched it shall spring to the fully open position within four seconds. Fully open is 
defined as vertical, upright position (80
 or more) from the closed position. The lid must open
without operator or electrical assistance, toward the back of the hood.
 The lid of the pressure fryer, when it is open, shall not block fire-extinguishing nozzle from the vat.
 The lid of a pressure fryer should be checked for proper operation at least once a month. If the lid
fails to fully open when unlatched or released, it should be repaired immediately by factory 
authorized service personnel. Do not operate a fryer with a defective lid opening mechanism. 
 Fryers with lids (other than pressure fryers) shall be operated only with the lid removed. Lids may
be used for covering the vat when power to the cooking appliance and hood has been turned off.
Sandwich Grills
 Sandwich grills acceptable for use with this hood shall be used such that when the lid is either
fully open, released, or unlatched it shall spring to the fully open position. Fully open is defined as 
vertical, upright position (80
 or more) from the closed position. The lid must open toward the
back of the hood. The lid of a sandwich grill, when open shall not block fire extinguishing nozzles 
from the cooking surface. 