The device is intended for installation in control panels and cabinet doors. The control
panels and consoles should be accessible from the back for mounting and operation (plug
connectors). The device can be installed in control cabinets with wall thicknesses of 2...13
mm. We recommend at least 3 mm for proper mounting with front IP65 protection.
Warning:
Preventing overheating during operation: The device should not be exposed to
direct sunlight or other sources of light.
Measures to prevent heat accumulation should be implemented if the device is
installed in a console, casing or similar enclosing structure. The maximum
permissible ambient temperature should not be exceeded.
Devices with drives should only be installed in an upright position. Any deviations
from this should be agreed upon with ads-tec GmbH.
The front is only IP65 protected if mounted correctly.
If the device is delivered with a CD/DVD-ROM drive, then there should be
sufficient space provided (approx. 130 mm) on the left side (as seen from the
front) to open the drive.