A R C H I T E C T U R A L A N D E N G I N E E R I N G S P E C

I N S T A L L A T I O N O F A L A R M

The combination smoke and carbon monoxide alarm shall be a BRK Model SCO2B and
shall provide at a minimum the following features and functions:
1. An ionization smoke sensing chamber and an electrochemical CO sensor.
2. Powered by a supervised 9V alkaline battery and features a solid state piezo horn

rated at 85dB at 10 ft. and the unit shall be capable of self restoring.

3. The unit shall perform self diagnostic tests and issue a malfunction warning (three

chirps) if the unit malfunctions.

4. The unit shall have an "End of Life" signal. This signal should be capable of

temporarily being silenced for up to 2 days. After about 2 days, the signal will

resume. After about 2-3 weeks the signal cannot be silenced.

5. A visual power-on indicator to confirm unit is receiving power. Separate LED 's to

indicate a smoke or CO alarm.

6. The CO sensor is adjusted not to detect CO levels below 30 PPM and will not

alarm when exposed to constant levels of 30 PPM for 30 days. It will alarm

at the following levels: 400 PPM CO between 4 and 15 minutes, 150 PPM CO

between 10 and 50 minutes and 70 PPM CO between 60 and 240 minutes.

7. Two Latching features: Alarm Latch to easily identify initiating alarm after alarm

condition has subsided. Low battery latch: to visually identify which unit is in low

battery condition. Two Silence Features: Alarm Silence to temporarily silence

nuisance alarms. Low Battery Silence to silence low battery chirp for up to 8 hours.

8. Two Locking features - tamper resistant locking pins that lock battery drawer

and/or alarm to mounting bracket.

9. The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and

relative humidity between 10% and 95%.

10. The unit shall contain mounting hardware and shall be listed for wall or ceiling

mounting.

11. The unit shall at a minimum meet the requirements of UL217 and UL2034,

CSFM, NFPA 72 and 720 and the ICC.

S H I P P I N G S P E C S :

T E C H N I C A L S P E C S

Individual Carton Dimensions

5.69"L x 2.25"W x 5.59"H

Weight

0.59 lbs.

Cube

0.041 ft3

UPC

0 29054 00089 7: SCO2B

0 29054 00736 0: SCO2LB

Master Carton Dimensions

14.43"L x 6.19"W x 12.63"H

Master Pack

12

Weight

7.6 lbs.

Cube:

0.65 ft3

I2of5:

200 29054 00089 1: SCO2B

800 29054 00736 6: SCO2LB

Pallet Information

Cases per Layer

19

Number of Layers:

3

Cases per Pallet:

57

Units per pallet:

684

Cube:

42.2 ft3

Weight:

498 lbs.

Alarm Dimensions:

5.6” dia x 2.0”H

Weight:

7.6 oz

Operating Voltage:

9V battery powered

Temperature Range:

40°F (4°C) to 100°F (38°C)

Humidity Range:

10% to 95% relative humidity (RH)

Audio Alarm:

85dB at 10 feet

Test/Silence:

Electronically simulates smoke condition or carbon

monoxide condition, causing the unit to alarm

Press and hold test/silence button

Alarm Reset:

Automatic when smoke and/or CO clears

Smoke Sensor:

Dual chamber ionization

CO Sensor:

Electrochemical

Indicator Lights/Sounds:
DC Power:

Intermittent Green LED

Local Alarm:

Red LED flashes rapidly

Alarm Latch:

Red LED flashes 2 sec on/2 sec off after local alarm stops

Low Battery Latch:

Green LED flashes on for 2 seconds, off for 2 seconds.

Note: Latching features are active for 15 minutes only.

Listing:

Listed to UL217 and UL2034 Standards

©2010 BRK Brands, Inc. a Jarden Corporation
Company (NYSE: JAH)

3901 Liberty Street Road
Aurora, IL 60504-8122
All rights reserved

First Alert is a registered trademark of the First Alert Trust
BRK is a registered trademark of BRK Brands, Inc.
CM3080

5.6"

TOP VIEW

SIDE VIEW

2.0"

CAT.

SCO2B/SCO2LB

MOUNTING

BRACKET

BATTERY DRAWER LOCK

Remove Pin

Push locking pin through

hole near battery drawer

on the back of the alarm.

Installation of this smoke alarm must conform to NFPA 72. Always check your local
building codes. Follow all instructions for placement as outlined in the user’s manual.

THE PARTS OF THIS SMOKE ALARM

BOTTOM OF ALARM

1.

Mounting bracket

2.

Mounting slots (1 of 2)

3.

Locking Pins

4.

Battery Drawer Latch

5.

Battery Drawer - Install

9V battery here

TOP OF ALARM

1.

Test/Silence Button

2.

Power Light (Green)/

Smoke Alarm light (Red)

3.

CO Alarm Light (Red)

4.

Battery Drawer

5.

Behind Cover: Alarm 85 dB horn

1

2

3

2

5

4

3