To Connect the Series Tap Plug Thermostat Kit:
a.
Connect the power cord of the heater to the
female side of the plug on the end of the
thermostat cord.
b.
Plug the male side of the series tap plug on the
thermostat cord into a three-wire (grounded)
electrical outlet within the building.
2.
To Connect the Direct Wired Thermostat Kit to the
Control Box on the Heater:
a.
The installation and wiring of a thermostat must
be done by an electrician or someone properly
qualified.
b.
Ensure that proper electrical gauge of wiring is
used to prevent voltage drop. Typically 18 gauge
is sufficient.
Action:
--
Disconnect and discard the yellow wire between
the 24 VAC output of the transformer and
terminal W on the ignition controller.
-- Remove the plastic hole plug at the bottom of
the control box and route the thermostat cord up
through this hole.
--
Connect the black lead of the thermostat’s
cordset to the 24 VAC output terminal of the
transformer.
--
Connect the white lead of the thermostat’s
cordset to terminal W of the ignition control.
--
Install the strain relief, included with the cordset,
into the hole previously occupied by the hole
plug..
WARNING
Electrical Shock Hazard
■
Disconnect the electrical supply before connecting the
thermostat to the heater.
■
Failure to follow this warning can result in electrical
shock, leading to personal injury or death.
10
THERMOSTAT INSTALLATION
MANUAL SHUT-OFF VALVE, HOSE
AND REGULATOR ASSEMBLY
REGULATOR
NIPPLE
VALVE, MANUAL
SHUT-OFF
GAS HOSE
ADAPTER
SEDIMENT TRAP
TO CONTROL
VALVE INLET
REGULATOR VENT
GAS FLO
W
1.
Always use approved pipe thread compound suitable
for use with L.P. gas or natural gas on the threaded
connections.
2.
Assemble the components together according to the
figure. This view is to show general assembly of the
components only. The regulator must always be
mounted so its vent, regardless of location on the
regulator, is always pointed downward.
3.
Tighten all connections securely.
4.
Check all connections for gas leaks using approved
gas leak detectors.
FIG. 5