Operating the generator, Starting the engine, Connecting electrical loads – Briggs & Stratton PRO6500 User Manual
Page 9: Stopping the engine, Caution, Warning
OPERATING THE
GENERATOR
Starting the Engine
Disconnect all electrical loads from the generator. Use the
following start instruction steps in numerical order:
1.
Make sure unit is on a level surface.
IMPORTANT: Failure to start and operate unit on a level
surface will cause the unit not to start or shut down during
operation.
2.
Turn fuel valve to “On” position (Figure 4).
3.
Make sure Idle Control switch is in “Off” position
(Figure 5).
4.
Follow start instructions given in engine owner’s manual.
NOTE: If engine starts after 3 pulls but fails to run, or if
unit shuts down during operation, make sure unit is on a
level surface and check for proper oil level in crankcase.
This unit may be equipped with a low oil protection device.
See engine manual.
Connecting Electrical Loads
• Let engine stabilize and warm up for a few minutes after
starting.
• Plug in and turn on the desired 120 and/or 240 Volt AC,
single phase, 60 Hz electrical loads.
• DO NOT connect 240 Volt loads to the 120 Volt duplex
receptacles.
• DO NOT connect 3–phase loads to the generator.
• DO NOT connect 50 Hz loads to the generator.
• DO NOT OVERLOAD THE GENERATOR. See
“Don’t Overload Generator”.
Stopping the Engine
1.
Turn OFF and unplug ALL electrical loads from
generator panel receptacles. NEVER start or stop
engine with electrical devices plugged in and turned
ON.
2.
Move idle control switch to “Off” position.
3.
Let engine run at no-load for several minutes to
stabilize internal temperatures of engine and generator.
4.
Move fuel valve to “Off” position.
5.
Turn engine off according to instructions given in the
engine owner’s manual.
9
BSPP Generator
Figure 4 — Fuel Shut-off Valve
• See “Don’t Overload Generator”.
• Start generator and let engine stabilize before connecting
electrical loads.
• Connect electrical loads in OFF position, then turn ON for
operation.
• Turn electrical loads OFF and disconnect from generator
before stopping generator.
Exceeding generators wattage/amperage capacity can
damage generator and/or electrical devices connected
to it.
CAUTION
Figure 5 — Idle Control Switch
• DO NOT touch hot surfaces.
• Allow equipment to cool before touching.
• The generator must be at least 5 feet from structures having
combustible walls and/or other combustible materials.
• Keep at least 3 feet of clearance on all sides of generator for
adequate cooling, maintenance and servicing.
• In the State of California a spark arrester is required by law
(Section 4442 of the California Public Resources Code). Other
states may have similar laws. Federal laws apply on federal
lands. If you equip the muffler with a spark arrester, it must be
maintained in effective working order.
Running engines produce heat.Temperature of
muffler and nearby areas can reach or exceed
150°F (65°C).
Severe burns can occur on contact.
Combustible debris, such as leaves, grass, brush,
etc. can catch fire.
WARNING