5

Install Electrical Accessories

Refer to the individual instructions packaged with kits or
accessories when installing.

Start--Up

CAUTION

!

PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal

injury.
Wear safety glasses, protective clothing, and gloves when

handling refrigerant and observe the following:
S

Front seating service valves are equipped with Schrader valves.

CAUTION

!

ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental

damage.
Federal regulations require that you do not vent refrigerant to

the atmosphere. Recover during system repair or final unit

disposal.

CAUTION

!

UNIT OPERATION AND SAFETY HAZARD
Failure to follow this caution may result in personal injury,

equipment damage or improper operation.
S

Do not overcharge system with refrigerant.

S

Do not operate unit in a vacuum or at negative pressure.

S

Do not disable low pressure switch in scroll compressor

applications.

S

Compressor dome temperatures may be hot.

Follow these steps to properly start up system:

1. After system is evacuated, fully open liquid and vapor

service valves.

2. Unit is shipped with valve stem(s) front seated (closed) and

caps installed. Replace stem caps after system is opened to

refrigerant flow (back seated). Replace caps finger--tight and
tighten with wrench an additional 1/12 turn.

3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure set

point is below indoor ambient temperature.

5. Set room thermostat to HEAT or COOL and fan control to

ON or AUTO mode, as desired. Operate unit for 15

minutes. Check system refrigerant charge.

24 VAC HOT

R

C

W2

Y

G

R

C

RVS COOLING

C

W2

HP THERMOSTAT

TYPICAL

FAN COIL

HEAT

PUMP

G

O

E

W2

E

W3

R

Y

24 VAC COM

HEAT STAGE 2

COOL/HEAT

STAGE 1

INDOOR FAN

EMERGENCY

HEAT

O

*
*
*

IF AVAILABLE

*

LEGEND

24-V FACTORY WIRING

24-V FIELD WIRING

FIELD SPLICE CONNECTION

OUTDOOR THERMOSTAT

EMERGENCY HEAT RELAY

SUPPLEMENTAL HEAT RELAY

SHR

EHR

ODT

A02325 / A97413

Fig. 8 -- Generic Wiring Diagrams

(See Thermostat Installation Instructions for specific unit com-

binations)

Sequence of Operation

Turn on power to indoor and outdoor units. Transformer is

energized.
Cooling
On a call for cooling, thermostat makes circuits R--O and R--Y, and

R--G. Circuit R--O energizes reversing valve, switching it to
cooling position. Circuit R--Y energizes contactor, starting outdoor

fan motor and compressor circuit. R--G energizes indoor unit
blower relay, starting indoor blower motor on high speed.
When thermostat is satisfied, its contacts open, de--energizing
contactor and blower relay. Compressor and motors should stop.
NOTE: If indoor unit is equipped with a time--delay relay circuit,
the indoor blower will run an additional 90 seconds to increase
system efficiency.

Heating

On a call for heating, thermostat makes circuits R--Y and R--G.

Circuit R--Y energizes contactor, starting outdoor fan motor and
compressor. Circuit R--G energizes indoor blower relay, starting

blower motor on high speed.
Should temperature continue to fall, R--W2 is made through
second--stage room thermostat. Circuit R--W2 energizes a relay,

bringing on first bank of supplemental electric heat and providing
electrical potential to second heater relay (if used). If outdoor

temperature falls below setting of outdoor thermostat (field

installed option), contacts close to complete circuit and bring on
second bank of supplemental electric heat.
When thermostat is satisfied, its contacts open, de--energizing
contactor and relay. All heaters and motors should stop.

Defrost

The defrost control is a time/temperature control which includes a

field selectable (quick--connects located at board edge) time period
between defrost cycles (30, 60, or 90 minutes), factory set to 90

minutes.

213A

/214A