Summary of registers, System data 0x0010h r/w agm system setup data, Data type abbreviations – Bacharach AGM300 User Manual
Page 78

70
Instruction 3015-4275
Summary of Registers
Register
Name
Number Type
Description
System Data
0x0010h
R/W
AGM System Setup Data
Status
0x0011h R/W
Operating summary of faults, alarms
and
status
Zone Data
0x12xxh
R/W
Setup data for up to 16 zones (xx
defines
zone
number)
CAL Data
0x0014h
R/W
Cal Factors for all gases
Date/Time
0x0015h
R/W
Set AGM300 date & time
Sensor Data
0x0016h
R
Raw measurement of sensors
Rel. Hold
0x0017h
W
Release AGM300 out of hold mode
Hold Zone
0x0018h
W
Put AGM300 into hold mode
Fault Log
0x19xxh
R
20 most recent fault events (xx = 00
or 01)
Alarm Log
0x1Axxh
R
20 most recent alarm events (xx = 00,
01,
or
02)
Serv. Mode
0x001Bh
W
Puts AGM300 into service mode
Rel Serv.
0x001Ch
W
Release AGM300 from service mode
PPM
0x001Eh
R
PPM values for all zones
Zone Log
0x3yxxh
R
Trend data for each AGM300 zone (y
= zone number (starting at 0), xx = 00 – 06)Data
Data Type Abbreviations
C ...................... Character
Float ................. Floating Point
I ........................ Integer
TIM................... Time
UC.................... Unsigned Character
UI ..................... Unsigned Integer