beautypg.com

Regulatory information for smoke/co alarms – BRK electronic SC7010B User Manual

Page 9

background image

9

REGULATORY INFORMATION FOR
SMOKE/CO ALARMS

REGULATORY INFORMATION FOR CO ALARMS

WHAT LEVELS OF CO CAUSE AN ALARM?
Underwriters Laboratories Inc. Standard UL2034 requires residential CO
Alarms to sound when exposed to levels of CO and exposure times as
described below. They are measured in parts per million (ppm) of CO
over time (in minutes).

UL2034 Required Alarm Points*:

• If the alarm is exposed to 400 ppm of CO, IT MUST ALARM

BETWEEN 4 and 15 MINUTES.

• If the alarm is exposed to 150 ppm of CO, IT MUST ALARM

BETWEEN 10 and 50 MINUTES.

• If the alarm is exposed to 70 ppm of CO, IT MUST ALARM

BETWEEN 60 and 240 MINUTES.

* Approximately 10% COHb exposure at levels of 10% to 95% Relative
Humidity (RH).
The unit is designed not to alarm when exposed to a constant level
of 30 ppm for 30 days.

CO Alarms are designed to alarm before there is an immediate life
threat. Since you cannot see or smell CO, never assume it’s not present.

An exposure to 100 ppm of CO for 20 minutes may not affect
average, healthy adults, but after 4 hours the same level may cause
headaches.

An exposure to 400 ppm of CO may cause headaches in average,
healthy adults after 35 minutes, but can cause death after 2 hours.

Standards: Underwriters Laboratories Inc. Single and Multiple Station
carbon monoxide alarms UL2034.

According to Underwriters Laboratories Inc. UL2034, Section 1-1.2:
“Carbon monoxide alarms covered by these requirements are intended
to respond to the presence of carbon monoxide from sources such as,
but not limited to, exhaust from internal-combustion engines, abnormal
operation of fuel-fired appliances, and fireplaces. CO Alarms are intended
to alarm at carbon monoxide levels below those that could cause a loss
of ability to react to the dangers of Carbon Monoxide exposure.” This CO
Alarm monitors the air at the Alarm, and is designed to alarm before CO
levels become life threatening. This allows you precious time to leave
the house and correct the problem. This is only possible if Alarms are
located, installed, and maintained as described in this manual.

Gas Detection at Typical Temperature and Humidity Ranges: The
CO Alarm is not formulated to detect CO levels below 30 ppm typically.
UL tested for false alarm resistance to Methane (500 ppm), Butane (300
ppm), Heptane (500 ppm), Ethyl Acetate (200 ppm), Isopropyl Alcohol
(200 ppm) and Carbon Dioxide (5000 ppm). Values measure gas and
vapor concentrations in parts per million.

Audible Alarm: 85 dB minimum at 10 feet (3 meters).

INSTALLING SMOKE ALARMS IN MOBILE HOMES
For minimum security install one Smoke Alarm as close to each
sleeping area as possible. For more security, put one unit in each room.
Many older mobile homes (especially those built before 1978) have little
or no insulation. If your mobile home is not well insulated, or if you are
unsure of the amount of insulation, it is important to install units on
inside walls only. Smoke Alarms should be installed where temperatures
normally remain between 40˚ F (4˚ C) and 100˚ F (38˚ C).

REGULATORY INFORMATION FOR SMOKE ALARMS

RECOMMENDED LOCATIONS FOR SMOKE ALARMS

Installing Smoke Alarms in Single-Family Residences

The National Fire Protection Association (NFPA), recommends one Smoke
Alarm on every floor, in every sleeping area, and in every bedroom.
In new construction, the Smoke Alarms must be AC powered and
interconnected. See “Agency Placement Recommendations” for details.
For additional coverage, it is recommended that you install a Smoke
Alarm in all rooms, halls, storage areas, finished attics, and basements,
where temperatures normally remain between 40˚ F (4˚ C) and 100˚ F
(38˚ C). Make sure no door or other obstruction could keep smoke
from reaching the Smoke Alarms.

More specifically, install Smoke Alarms:

On every level of your home, including finished attics and basements.

Inside every bedroom, especially if people sleep with the door partly
or completely closed.

In the hall near every sleeping area. If your home has multiple
sleeping areas, install a unit in each. If a hall is more than 40 feet
long (12 meters), install a unit at each end.

At the top of the first-to-second floor stairway, and at the bottom
of the basement stairway.

Specific requirements for Smoke Alarm installation vary from state to
state and from region to region. Check with your local Fire Department
for current requirements in your area. It is recommended AC or AC/DC
units be interconnected for added protection.

AGENCY PLACEMENT RECOMMENDATIONS

Standards: Underwriters Laboratories Inc. Single and Multiple Station
Smoke Alarms 217.

NFPA 72 (National Fire Code) Chapter 11
“For your information, the National Fire Protection Association's
Standard 72, reads as follows:”

“11.5.1 One- and Two-Family Dwelling Units.”

“11.5.1.1 Smoke Detection.

Where required by applicable laws, codes,

or standards for the specified occupancy, approved single- and multiple-
station Smoke Alarms shall be installed as follows: (1) In all sleeping
rooms Exception: Smoke Alarms shall not be required in sleeping rooms
in existing one- and two-family dwelling units. (2) Outside of each
separate sleeping area, in immediate vicinity of the sleeping rooms.
(3) On each level of the dwelling unit, including basements Exception:
In existing one- and two family dwelling units, approved Smoke Alarms
powered by batteries are permitted.”

“A.11.8.3 Are More Smoke Alarms Desirable?
The required number of Smoke Alarms might not provide reliable early
warning protection for those areas separated by a door from the areas
protected by the required Smoke Alarms. For this reason, it is recom-
mended that the householder consider the use of additional Smoke
Alarms for those areas for increased protection. The additional areas
include the basement, bedrooms, dining room, furnace room, utility
room, and hallways not protected by the required Smoke Alarms. The
installation of Smoke Alarms in kitchens, unfinished attics, or garages is
not normally recommended, as these locations occasionally experience
conditions that can result in improper operation.”

California State Fire Marshal (CSFM)
Early warning detection is best achieved by the installation of fire
detection equipment in all rooms and areas of the household as follows:
A Smoke Alarm installed in each separate sleeping area (in the vicinity,
but outside bedrooms), and Heat or Smoke Alarms in the living rooms,
dining rooms, bedrooms, kitchens, hallways, finished attics, furnace
rooms, closets, utility and storage rooms, basements, and attached
garages.

RECOMMENDED LOCATIONS FOR SMOKE ALARMS, Continued