Figure 3 – Air Tube Mounting Dimensions

Legen

d

D

Air Tube Diameter

E

Minimum insertion depth

G

Air tube to inside of chamber: 1/4” ± 1/8”

T

Air Tube Length

Air Tube Combination Codes

Model

Tube

Dimension

T

Dimension

D

Code

Dimension

E

CF2500A/

CF2500

KP

6-3/4”

6-1/2”

CF 66 KP

3-1/4”

10-1/4”

6-1/2”

CF 102 KP

3-1/4”

13-3/4”

6-1/2”

CF 136 KP

3-1/4”

17-3/4”

6-1/2”

CF 176 KP

3-1/4”

CF3500

KM

8”

8”

CF 80 KM

4-1/2”

9-1/4”

8”

CF 92 KM

4-1/2”

11-1/2”

8”

CF 114 KM

4-1/2”

15”

8”

CF 150 KM

4-1/2”

19”

8”

CF 190 KM

4-1/2”

KR

11-1/2”

9-15/16”

CF 114 KR

5-1/8”

14”

9-15/16”

CF 140 KR

5-1/8”

19”

9-15/16”

CF 190 KR

5-1/8”

1)

Install the burner with a 2

o

pitch as shown.

Firing Rate

(gph)

Minimum Dimensions

A

L

17

10.5”

48.0”

22

11.5”

58.0”

27

12.5”

66.0”

32

12.5”

73.0”

35

13.0”

77.0”

Figure 2 – Chamber Dimensions

2305

A

L

T

G

E

D

2

o

1)

Verify Air Tube

The information in this section may be disregarded if the
air tube is supplied by the appliance manufacturer.

The following tube arrangements are available –

CF2500 - Tube KP -17.0.0 to 19.9 GPH
CF2500A - Tube KP -17.0 to 25.0 GPH
CF3500A - Tube KM -17.0 to 35.0 GPH or

Tube KR -17.0 to 35.0 GPH

Maximum fi ring capacity depends on the fi rebox
pressure. Use Table 2 to verify the correct air tube type
for the fi ring rate required. (Tube KR [CF3500A] is an
optional air tube combination for maximum capacity rate.
It requires a larger I.D. fl ange Number 51631.)

See Figure 3 to verify the correct air tube length and air
tube combination code.



Section: Pre-installation Checklist