TABLE 7

PRESSURE TABLE

COOLING

Air Temperature Entering Outdoor Coil °F

W12A

à

TABLE 8

OPTIONAL FIELD INSTALLED ACCESSORIES

Model

Return Air

Temperature Pressure

75°

80°

85°

90°

95°

100°

105°

100°

115°

W12Aà

75 deg. DB

62 deg. WB

Low Side

High Side

120

291

124

310

129

332

133

355

136

379

138

405

141

432

142

460

143

490

80 deg. DB

67 deg. WB

Low Side

High Side

128

298

133

318

138

340

142

364

143

387

148

415

151

443

152

472

153

503

85 deg. DB

72 deg. WB

Low Side

High Side

132

308

138

329

143

352

147

377

150

403

153

430

156

459

157

489

158

521

Model

Description

BOP-1A

Blank Off Plate

X

BFAD-1

Barometric Fresh Air Damper

X

EIFM-1

Economizer with Exhaust

X

CMA-28

Low Ambient Control

X

CRVS-1

Commercial Ventilator - Spring Return

X

Low Side Pressure +4 PSIG

High Side Pressure +10 PSIG