ADJUSTMENTS

Adjustable Delay on Make and Delay on Break

Timer
The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes. Delay of Make (DOM)
timing on power up and after power interruptions is equal
to 2 minutes plus 10% of Delay of Break (DOB) setting:

0.5 minute (30 seconds)

DOB = 123 second DOM

1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with not delay.

Typical Settings for Dual Unit Installation:
Unit No. 1: DOB set at 2 minutes, and DOM is 132
seconds.

Unit No. 2: DOB set at 4 minutes, and DOM is 144
seconds.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on
all units so that the system operating pressures can be
observed. Pressure chart can be found later in the manual
covering all models. It is imperative to match the correct
pressure chart to the unit by model number.