MINIMUM CLEARANCES

NOTE: These boilers are intended to be installed in a room which is large compared to the size of
the boiler. They are not intended for alcove installation and are suitable for installation on non-
combustible flooring only.



DIMENSION

D-SERIES F-SERIES

1

CL-SERIES

K-SERIES

RV, RW & AB SERIES

WATER/

STEAM

TO 50#

STEAM

OVER

50#

WATER

/STEAM

TO 50#

STEAM

OVER

50#

WATER

/STEAM

TO 50#

STEAM

OVER

50#

WATER

/STEAM

TO 50#

STEAM

OVER

50#

WATER

/STEAM

TO 50#

STEAM

OVER

50#

A 18"

36"

18"

48"

24"

24"

18"

36"

24"

24"

B 24"

24"

48"

96"

48"

36"

48"

24"

48"

48"

C

V

& C

H

18" 36" 18" 36" 24" 24" 24" 24" 24" 24"

D 48"

96"

18"

36"

24"

24"

24"

24"

24"

24"

E

L

& E

R

24" 24" 18" 36" 24" 24" 24" 24" 32" 32"

1 - F-Series boilers are approved for installation on combustible flooring. Do not install on carpeting.

A - Clearance above boiler

B - Front of boiler

C

V

- Clearance from gas vent, measured vertically above pipe

C

H

- Clearance from gas vent, measured horizontally or below pipe

D - From back of boiler

E

L

- Left side of boiler

E

R

- Right side of boiler


These clearances are general minimum clearances. Local codes may dictate larger clearances.