Minimum clearances – Bryan Boilers Forced Draft Steam Boilers User Manual
Page 3
MINIMUM CLEARANCES
NOTE: These boilers are intended to be installed in a room which is large compared to the size of
the boiler. They are not intended for alcove installation and are suitable for installation on non-
combustible flooring only.
DIMENSION
D-SERIES F-SERIES
1
CL-SERIES
K-SERIES
RV, RW & AB SERIES
WATER/
STEAM
TO 50#
STEAM
OVER
50#
WATER
/STEAM
TO 50#
STEAM
OVER
50#
WATER
/STEAM
TO 50#
STEAM
OVER
50#
WATER
/STEAM
TO 50#
STEAM
OVER
50#
WATER
/STEAM
TO 50#
STEAM
OVER
50#
A 18"
36"
18"
48"
24"
24"
18"
36"
24"
24"
B 24"
24"
48"
96"
48"
36"
48"
24"
48"
48"
C
V
& C
H
18" 36" 18" 36" 24" 24" 24" 24" 24" 24"
D 48"
96"
18"
36"
24"
24"
24"
24"
24"
24"
E
L
& E
R
24" 24" 18" 36" 24" 24" 24" 24" 32" 32"
1 - F-Series boilers are approved for installation on combustible flooring. Do not install on carpeting.
A - Clearance above boiler
B - Front of boiler
C
V
- Clearance from gas vent, measured vertically above pipe
C
H
- Clearance from gas vent, measured horizontally or below pipe
D - From back of boiler
E
L
- Left side of boiler
E
R
- Right side of boiler
These clearances are general minimum clearances. Local codes may dictate larger clearances.