24 VAC HOT

24 VAC COM

R

C

G

W/W1

Y/Y2

R

C

C

A/C

THERMOSTAT

Typical

FAN COIL

AIR

CONDITIONER

G

W2

HEAT STAGE 1

COOL STAGE 1

INDOOR FAN

24 VAC HOT

24 VAC COM

R

C

G

W/W1

Y/Y2

R

C

C

A/C

THERMOSTAT

Typical

FURNACE

AIR

CONDITIONER

Y

G

W

HEAT STAGE 1

COOL STAGE 1

INDOOR FAN

A02326

LEGEND

24-V FACTORY WIRING

24-V FIELD WIRING

FIELD SPLICE CONNECTION

CONTACTOR

C

A97368

Fig. 7 -- Generic Wiring Diagrams

(See Thermostat Installation Instruction

for specific unit combinations)

PURONR (R--410A) REFRIGERANT QUICK REFERENCE GUIDE

S

Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement

components are designed to operate with Puron refrigerant

S

Puron refrigerant cylinders are rose colored.

S

Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.

S

Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose

when charging into suction line with compressor operating

S

Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low--side retard.

S

Use hoses with 700 psig service pressure rating.

S

Leak detectors should be designed to detect HFC refrigerant.

S

Puron refrigerant, as with other HFCs, is only compatible with POE oils.

S

Vacuum pumps will not remove moisture from oil.

S

Do not use liquid--line filter driers with rated working pressures less than 600 psig.

S

Do not leave Puron suction line filter driers in line longer than 72 hours.

S

Do not install a suction--line filter drier in liquid line.

S

POE oils absorb moisture rapidly. Do not expose oil to atmosphere.

S

POE oils may cause damage to certain plastics and roofing materials.

S

Wrap all filter driers and service valves with wet cloth when brazing.

S

A factory approved liquid--line filter drier is required on every unit.

S

Do NOT use an R--22 TXV.

S

If indoor unit is equipped with an R--22 TXV or piston metering device, it must be changed to a hard shutoff Puron TXV.

S

Never open system to atmosphere while it is under a vacuum.

S

When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter driers.

Evacuate to 500 microns prior to recharging.

S

Do not vent Puron refrigerant into the atmosphere.

S

Do not use capillary tube coils.

S

Observe all warnings, cautions, and bold text.

S

All indoor coils must be installed with a hard shutoff Puron TXV metering device.