Bryant, Serial model – Bryant Packaged Air Handling Units 542J User Manual
Page 3
3
SERIAL
MODEL
Compressors
(Factory Charged)
Refrigerant/System
Qty Volts AC
PH Hz RLA LRA
lbs kg R —
Test Pressure Gage
Hi
PSI ( kPa)
SERIAL
MODEL
1
2
Fan Motors
Qty
PH Hz
FLA
HP
KW
Volts AC
Power
Supply
Max
Volts
Min
Volts
PH
MCA *
MOCP *
Hz
Volts AC
= Min Circuit Amps
* MOCP = Max Over Current Protective Device Amps
* MCA
(Fuse or HACR Bkr.)
Test with External Static
in H20
kPa
NOT Suitable for Outdoor Use
Designed in U.S.A.
Assembled in Mexico
Part Number/Rev
Charge System per Installation Instructions
99NA504644/2.0
BRYANT
5
1
2
2
6
7
A
8
0
10
4
3
J
4
E
5
1
6
0
9
0
11
A
12
1
13
0
14
A
15
A
16
A
17
Model Number
Position of Digit
524JE16A000A10AAA
C11004
Fig. 2 -- Example of Nameplate with Model Number
Table 1 – Electrical Data, Standard Motors
UNIT
V---PH---Hz
{
VOLTAGE
LIMITS
FAN MOTOR
POWER SUPPLY
Hp (kW)
FLA
Minimum
Circuit Amps
MOCP
524J
*
16A
524J
*
16H
208/230---3---60
187---253
3.7 (2.76)
10.6
13.3
20
460---3---60
414---506
3.7 (2.76)
4.6
6.0
15
575---3---60
518---632
3.0 (2.24)
3.8
4.8
15
524J*25A
524J*25H
208/230---3---60
187---253
5.0 (3.73)
14.6/12.8
18.3/16.0
30/25
460---3---60
414---506
5.0 (3.73)
6.4
8.0
15
575---3---60
518---632
5.0 (3.73)
5.1
6.4
15
524J*28A
208/230---3---60
187---253
7.5 (5.59)
21.4/19.4
26.9/24.3
45/40
460---3---60
414---506
7.5 (5.59)
9.7
12.1
20
575---3---60
518---632
7.5 (5.59)
7.8
9.8
15
524J*30A
208/230---3---60
187---253
10.0 (7.46)
28.2/26.8
35.3/33.5
60/60
460---3---60
414---506
10.0 (7.46)
13.4
16.8
30
575---3---60
518---632
10.0 (7.46)
10.3
12.9
20
NOTE: See page 5 for table legend and notes