beautypg.com

Bryant, Serial model – Bryant Packaged Air Handling Units 542J User Manual

Page 3

background image

3

SERIAL

MODEL

Compressors

(Factory Charged)

Refrigerant/System

Qty Volts AC

PH Hz RLA LRA

lbs kg R —

Test Pressure Gage

Hi

PSI ( kPa)

SERIAL

MODEL

1

2

Fan Motors

Qty

PH Hz

FLA

HP

KW

Volts AC

Power
Supply

Max
Volts

Min
Volts

PH

MCA *

MOCP *

Hz

Volts AC

= Min Circuit Amps

* MOCP = Max Over Current Protective Device Amps

* MCA

(Fuse or HACR Bkr.)

Test with External Static

in H20

kPa

NOT Suitable for Outdoor Use

Designed in U.S.A.
Assembled in Mexico

Part Number/Rev

Charge System per Installation Instructions

99NA504644/2.0

BRYANT

5

1

2

2

6

7

A

8

0

10

4

3

J

4

E

5

1

6

0

9

0

11

A

12

1

13

0

14

A

15

A

16

A

17

Model Number

Position of Digit

524JE16A000A10AAA

C11004

Fig. 2 -- Example of Nameplate with Model Number

Table 1 – Electrical Data, Standard Motors

UNIT

V---PH---Hz

{

VOLTAGE

LIMITS

FAN MOTOR

POWER SUPPLY

Hp (kW)

FLA

Minimum

Circuit Amps

MOCP

524J

*

16A

524J

*

16H

208/230---3---60

187---253

3.7 (2.76)

10.6

13.3

20

460---3---60

414---506

3.7 (2.76)

4.6

6.0

15

575---3---60

518---632

3.0 (2.24)

3.8

4.8

15

524J*25A

524J*25H

208/230---3---60

187---253

5.0 (3.73)

14.6/12.8

18.3/16.0

30/25

460---3---60

414---506

5.0 (3.73)

6.4

8.0

15

575---3---60

518---632

5.0 (3.73)

5.1

6.4

15

524J*28A

208/230---3---60

187---253

7.5 (5.59)

21.4/19.4

26.9/24.3

45/40

460---3---60

414---506

7.5 (5.59)

9.7

12.1

20

575---3---60

518---632

7.5 (5.59)

7.8

9.8

15

524J*30A

208/230---3---60

187---253

10.0 (7.46)

28.2/26.8

35.3/33.5

60/60

460---3---60

414---506

10.0 (7.46)

13.4

16.8

30

575---3---60

518---632

10.0 (7.46)

10.3

12.9

20

NOTE: See page 5 for table legend and notes