Specifications, Carefree ratings, Dimensions – Burnham Carefree DOE User Manual

Page 2: Standard equipment

background image

Form No. PL81401361000-5/04-5Ms

Printed in the U.S.A.

© 2004 U.S. Boiler Company, Inc. - Lancaster, PA

Phone: 717-397-4701

www.burnham.com

SPECIFICATIONS

Note: DOE Heating Capacity ratings are shown. Where the boiler and piping are in the heated space, the boiler may be selected on the basis of the

Heating Capacity. Where a piping loss and/or pick up loss will exist, add this loss to the building loss to determine the total heating requirement.

Where a piping loss only will exist but cannot be calculated, multiply the calculated building loss by a 1.15 factor to determine the total heating

requirement. Design Working Pressure: 30 PSIG, Water Only.

Dimensions

(in inches)

Standard Equipment

Deluxe blue jacket

Field wiring terminal block

Wall mounting brackets

Thermostat terminal block

Heating element sequencers

Dual high limit control

Neon indicator lights

Pressure temperature gauge

Circulator delay control

Safety relief valve

Circulator switch control

Boiler drain valve

circuit fuse

Internal wiring

Transformer - 120/24V-40VA

Heating element relays

* For runs in excess of 50 ft. consult local and national electrical codes.

CAREFREE RATINGS

* Closet installation requires two ventilation openings, one located at top and one at

bottom, each opening to have 25 sq. in. net free area.

Recommended Power Supply to Boiler

Clearance Requirements

Boiler

Model

DOE Heating Capacity MBH

AMPS

(240V)

Water Flow Rate — GPM

Based on 20°F Temp. Rise

and Boiler Capacity at:

Approx.

Shipping

Weignt Lbs..

AFUE%

240V

220V

208V

240V

220V

208V

E-412

E-416

E-420

41

55

68

35

46

58

31

41

52

50

70

85

4.1

5.5

6.8

3.5

4.6

5.8

3.1

4.2

5.2

133

133

133

100

100

100

Boiler Model

KW

AMPS Volts Phase

No./Size of

Elements

Minimum*

Wire Size

Maximum

Fuse Size (AMPS)

Approx. Weight

Full Lbs.

Water Content

Gals.

E-412

E-416

E-420

12

16

20

50

70

85

240/1

240/1

240/1

4-3KW

2-3KW, 2-5KW

4-5KW

6

4

2

60

80

90

155

155

155

3-1/2

3-1/2

3-1/2

For Service

Accessability

(in inches)

Approved for Closet and Alcove Installation

with Minimum Clearance to Combustible Material*

(in inches)

Left Side

Right Side

Top

Bottom

Rear

Front

18

6

9

9

0

For Door

Removal

18

0

9

15

0

2" Closet

18" Alcove