beautypg.com

Burnham MST288 User Manual

Page 4

background image

© 2007 U.S. Boiler Company, Inc. - Lancaster, PA

Phone: 1-888-432-8887

Printed in the U.S.A.

Form No. PL81401302000-2/07-20Mss

Boiler

Model

Burner

Firing Rate

DOE

Heating

Capacity

MBH

2

I=B=R Net

Ratings

Flue

Collar

Diam.

Inches

4

Minimum Chimney

Requirements

AFUE %

Water

Content

(Heater)

to NWL

Gallons

GPH

MBH

1

Steam

MBH

3

Steam

Sq. Ft.

Round

In. Diam.

Rectangle

In. x In.

Height

Feet

MST288

0.75

105

92

69

288

6

6

8 x 8

15

86.0

15.3

MST396

1.05

147

127

96

396

6

6

8 x 8

15

86.0

15.3

MST513

1.35

189

164

123

513

6

6

8 x 8

15

86.0

19.7

MST629

1.65

231

201

151

629

7

7

8 x 8

15

86.0

24.1

Ratings

Optional Tankless Heater Ratings

Dimensions

Notes: Maximum Working Pressure: 15 PSI Steam
1. The I=B=R Burner Capacity is based on oil having Higher Heating Value of 140, 000 BTU/Gal.
2. DOE Heating Capacity and Annual Fuel Utilization Efficiency (AFUE) are based on US Government tests at 13.0% CO

2

with No. 1 maximum smoke and 0.00” draft in

the breach on standard equipment package.
3. Net I=B=R Ratings are based upon pick-up allowance of 1.333. Consult manufacturer with unusual piping and pickup requirements before selecting boiler.
4. Used for sizing flue connection materials.

Boiler

Model

*222A Tankless Heater

Rating GPM

Pressure Drop PSI

MST288

3.00

22.0

MST396

3.25

24.3

MST513

3.50

26.5

MST629

4.00

31.0

Notes:
1. Tankless Heater Rating, GPM is based on 100 F temperature rise with
40 F inlet water (intermittent draw) with boiler water temperature of 190°F.

Boiler

Model

‘A’

‘B’

‘C’

‘D’

MST288

22-5/8

24

6

35-15/16

MST396

22-5/8

24

6

35-15/16

MST513

28-5/8

30

6

35-15/16

MST629

34-5/8

36

7

35-15/16

www.burnham.com

This manual is related to the following products: