DIRECT VENT - HORIZONTAL (CATEGORY III)

WARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the
safety and health of inhabitants.

• A maximum of two elbows can be used on inlet and outlet vent piping respectively. Each elbow is equal to 10 feet (3 m) of
straight pipe.

• Use only special gas vent pipes listed for use with Category III gas burning heaters, such as stainless steel Saf-T-Vent by Heat
Fab, Inc. Inc., available from A.O. Smith WPC, 5621 W. 115th Street, Alsip, IL 60803 Phone: 1-800-433-2545 or
Fax: 1-800-433-2515. Pipe joints must be positively sealed.

TABLE 10. DIRECT VENT (HORIZONTAL EXHAUST CONFIGURATIONS)

Figure 8.

APPLIANCE

CERTIFIED

VENT

MAXIMUM

AIR INTAKE

AIR INLET

MAXIMUM

MODEL

CATEGORY EXHAUST VENT

SIZE

VENT LENGTH

MATERIAL

SIZE

AIR INTAKE

MATERIAL

(INCHES)

(FEET)

(INCHES)

LENGTH (FEET)

GAL. STEEL

III

PVC, ABS OR

CPVC

GAL.STEEL

III

PVC, ABS CR

CPVC

GAL. STEEL

III

PVC, ABS OR

CPVC

GAL. STEEL

III

PVC, ABS OR

CPVC

GAL. STEEL

III

PVC, ABS OR

CPVC

I000

1300

1500

1850

2100

2500

STAINLESS

(SEALED)

STAINLESS

(SEALED)

STAINLESS

(SEALED)

STAINLESS

(SEALED)

STAINLESS

(SEALED)

10"

(25.4 cm)

12"

(30.5 cm)

14"

(35.6 cm)

14"

(35.6 cm)

16"

(40.6 cm)

35'

(10.7 m)

35'

(10.7 m)

20'

(6.1 m)

20'

(6.1 m)

20'

(6.1 m)

35'

(10.7 m)

35'

(10.7 m)

20'

(6.1 m)

20'

(6.1 m)

20'

(6.1 m)

8"

(20.3 cm)

10"

(25.4 cm)

10"

(25.4 cm)

12"

(30.5 cm)

12"

(30.5 cm)