DIRECT VENT - VERTICAL (CATEGORY I)

TABLE 9. DIRECT VENT (VERTICAL EXHAUST CONFIGURATIONS)

• Connection for the appliance exhaust vent to the stack must be as direct as possible. Maximum and minimum venting length
for Category I appliances shall be determined per the latest edition of the National Fuel Code (U.S.) and CAN/CSA-B149.1
and .2 Installation Code (Canada).

• The vent should be installed so as to prevent the accumulation of condensate and, where necessary, have means provided for
drainage of condensate. The horizontal breaching of a vent must have an upward slope of not less than 1/4 inch per linear foot
(2 cm/m) from the boiler to the vent terminal. The horizontal portion of the vent shall be supported to maintain clearances and to
prevent physical damage or separation of joints.

Figure 7.

APPLIANCE

CERTIFIED

EXHAUST VENT

MAXIMUM

AIR INTAKE

AIR INLET

MAXIMUM

MODEL

CATEGORY EXHAUST VENT SIZE (INCHES) EXHAUST VENT

MATERIAL

SIZE (INCHES)

AIR INTAKE

MATERIAL

LENGTH (FEET)

LENGTH (FEET)

GAL. STEEL

I

PVC, ABS OR

CPVC

GAL.STEEL

I

PVC, ABS CR

CPVC

GAL. STEEL

I

PVC, ABS OR

CPVC

GAL. STEEL

I

PVC, ABS OR

CPVC

GAL. STEEL

I

PVC, ABS OR

CPVC

I000

1300

1500

1850

2100

2500

TYPE B OR

EQUIVALENT

TYPE B OR

EQUIVALENT

TYPE B OR

EQUIVALENT

TYPE B OR

EQUIVALENT

TYPE B OR

EQUIVALENT

10"

(25.4 cm)

12"

(30.5 cm)

14"

(35.6 cm)

14"

(35.6 cm)

16"

(40.6 cm)

35'

(10.7 m)

35'

(10.7 m)

20'

(6.1 m)

20'

(6.1 m)

20'

(6.1 m)

35'

(10.7 m)

35'

(10.7 m)

20'

(6.1 m)

20'

(6.1 m)

20'

(6.1 m)

8"

(20.3 cm)

10"

(25.4 cm)

10"

(25.4 cm)

12"

(30.5 cm)

12"

(30.5 cm)