Page 9

background image

7

N

OTE

:

S

ETTINGS ARE MADE THROUGH SUPPLIED

P

OWER

C

HUTE SOFTWARE OR OPTIONAL

S

MART

S

LOT

ACCESSORY CARDS

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

Low Battery Warning.

PowerChute interface
software provides auto-
matic, unattended shut-
down when approxi-
mately two minutes (by
default) of battery oper-
ated run time remains.

Brightly lit: Low battery
warning interval is about two
minutes.
Dimly lit: Low battery
warning interval is about five
minutes.
Off: Low battery
warning interval is about
eight minutes.

Possible interval settings:
2, 5, 8, 11, 14, 17, 20, 23
minutes.

The low battery warning
beeps are continuous when
two minutes of run time
remain.

To change the warning in-
terval default setting, press
the voltage sensitivity button
(use a pointed object such as
a pen to do so), while press-

ing and holding the

button (front panel).

Synchronized Turn-on
Delay

0 seconds

60, 120, 180, 240, 300, 360,
420 seconds

The UPS will wait the speci-
fied time after the return of
utility power before turn-on
(to avoid branch circuit
overload).

High Transfer Point

230V models:
253VAC

120V models:
127VAC

100V models:
108VAC

230V models:
257, 261, 265VAC

120V models:
130, 133, 136VAC

100V models:
110, 112, 114VAC

To avoid unnecessary bat-
tery usage, set the high
transfer point higher if the
utility voltage is chronically
high and the connected
equipment is known to work
under this condition.

Low Transfer Point

230V models:
208VAC

120V models:
106VAC

100V models:
92VAC

230V models:
196, 200, 204VAC

120V models:
97, 100, 103VAC

100V models:
86, 88, 90VAC

Set the low transfer point
lower if the utility voltage is
chronically low and the con-
nected equipment can toler-
ate this condition.

Output Voltage

230V models:
230VAC

230V models:
220, 240VAC

230V models ONLY, allow
the user to select the output
voltage.