Option 1: UL 508a reference SB4.2
According to UL508A Supplement SB, if a panel 
contains no current-limiting devices, its SCCR 
depends on the “weakest” or lowest rated 
component or combination within the panel. 
However, Supplement SB also states that if current-
limiting fuses are used in the feeder circuit, and if the 
highest instantaneous current reached during the 
first half cycle of a fault is less than or equal to the 
lowest rated SCCR in any branch circuit, the SCCR 
of the current limiting fuse can be applied to the 
combination.
When the specified branch circuit protection related 
to the high fault short circuit current rating is a Class 
CC,G,J,L,RK1, RK5 or T fuse, a fuse of a different class 
is able to be used at the same high fault rating where 
the peak let through current and I2t of the new fuse 
is not greater than that of the specified fuse. 
Option 2: UL 508a reference SB4.3
An alternate method of achieving a high short circuit 
rating is by applying a power transformer with an 
isolated secondary winding, the short circuit current 
rating on the line side of the transformer shall be one 
of the following:
For a power transformer rated not more than 10 
kVA, and where the short circuit current rating of 
all components in the secondary circuit are not 
less than 5kA, the short circuit current rating of the 
primary overcurrent protective device is able to be 
assigned to the line side of the power transformer 
circuit.
For a power transformer rated not more that 5kVA 
and a 120V maximum secondary voltage, and where 
the short circuit current rating of all components in 
the secondary circuit are not less than 2kA, the short 
circuit rating of the primary overcurrent protective 
device is able to be assigned to the line side of the 
power transformer circuit.
Option 3: UL 508a reference SB4.2
The combinations listed in the linked spreadsheets 
(www.ul.com/controlequipment/shortcircuit.html)
may be applied in a manufacturer’s Listed industrial 
control panel without further evaluation or specific 
documentation in the manufacturer’s UL Procedure 
pages. 
The spreadsheets cover the application of individual 
components, including a disconnecting means, an 
over current protective device, motor controller 
and motor overload protection, as a combination 
motor controller having specified ratings, including 
a short-circuit current rating (SCCR). Each of the 
individual components is Listed or Recognized to the 
requirements in the applicable component Standard.
The specified ratings for the combination motor 
controller may be applied to the end-product 
equipment only when all of the specific components 
listed are provided in the end-product equipment 
and installed according to any applicable conditions 
of acceptability.
Components other than those identified in the 
combination motor controller and connected in the 
power circuit of the combination motor controller 
will require additional evaluation. 