Pfannenberg PWS Series User Manual
Page 12

PWS Series Air/Water Heat Exchangers
9
The characteristics of any additives or system water ought not to deviate greatly from the hydrological
data given below.
Hydrological Data
Model: Standard
Device Model: VA
pH value
7 - 8.5
6 - 9
Carboxylic Acid
°dH
> 3 < 8
1 - 12
Free carbonic acid
mg/dm3
8 - 15
1 - 100
Associated carbonic acid
mg/dm3
8 - 15
not present
Corrosive carbonic acid
mg/dm3
0
0 - 400
Sulphides
not present
not present
Oxygen
mg/dm3
< 10
< 10
Chloride ions
mg/dm3
< 50
< 200
Sulphate ions
mg/dm3
< 250
< 500
Nitrates and nitrites
mg/dm3
< 10
< 100
CSB
mg/dm3
< 7
< 40
Ammonia
mg/dm3
< 5
< 20
Iron
mg/dm3
< 0.2
not present
Manganese
mg/dm3
< 0.2
not present
Conductivity
mS/cm
< 2200
< 4000
Evaporation residue
mg/dm3
< 500
< 2000
Potassium permanganate
consumption
mg/dm3
< 25
< 40
Suspended matter
mg/dm3
< 3 > 3
< 15 split-stream cleansing
recommended > 15 constant
cleaning recommended