Approvals – Pfannenberg PATROL PA X 5 Series User Manual
Page 7
085 501 945d
30304-004d
7
Approvals
Approvals
(
valid for marked equipment)
Construction Product
Directive
(89/106/EWG)
VdS 0786-CPD-xxxxx
(in preparation)
Options
–SSM
Rated voltage
24V DC
Rated voltage range acc. to
EN54-3, EN54-23
18V – 57V
Option: -SSM: 18V – 30V
Tone
2
15
60
104
131
146
Compliant with the Construction Product Directive (89/106/EWG)
1200Hz-500Hz (Saw tooth) DIN/PFEER P.T.A.P.
500Hz-1200Hz (Slow whoop)
825Hz (Continuous)
660Hz (Intermittent tone)
800Hz/ 1000Hz (Alternating tone)
544Hz/ 440Hz (NF S 32-001)
Signaling area
EN54-3: see document 30304-005-1
Environmental
protection class
Type B (T
amb
-25°C…+55°C)
VdS
Gxxxxx, data see Construction Product Directive (89/106/EWG) (in preparation)
GL
GLxxxxx (in preparation)
Environmental Category C, H, EMC1
In preparation: UCST, UCST7, UEES, UEES7
(only 24V DC): ULSZ, ULSZ7
Rated
voltage
Fire Alarm Equipment
General Signal Equipment
PA 5
12 – 48V DC
24V AC
115V AC
230V AC
X
Special application limited voltage
range 18 – 57V DC
X
UL, cUL
PA X 5-05
PA X 5-10
12V DC
24V DC
48V DC
24V AC
115V AC
230V AC
X
UL specifications:
Suitable for indoor and outdoor use.
Signaling area: see document 30304-005-1
Cable gland entries:
Conduit installation needs to be UL/ cUL listed fittings suitable for knockout openings. The supply wiring has to be en-
closed in metal conduits for products for Fire Alarm Use.
According to CSA-C22.2 No. 205-M1983 clause 4.3.4 the connection is limited to max. seven leads for combined units
(PA X).
Installation:
The units shall be installed indoors or outdoors in accordance with the manufacturer’s installation instructions as well as
the National Electrical Code (NFPA 70) and the National Fire Alarm Code (NFPA 72) for the units evaluated for Public
Fire Alarm applications in the U.S. In Canada, they shall be installed in accordance with the Canadian Electrical Code,
Part 1 and the Standard for the Installation of Fire Alarm Systems CAN/ULC-S524-M91 for the units evaluated for Public
Fire Alarm applications. The installation shall also be in a manner acceptable with the local authority having jurisdiction.
For audible application for Fire Alarm Service use both terminals for connection. Break wire run to provide Electrical
Supervision (see UL 464 clause 39.1e). The tone no. 111 is to be used for evacuation use only (see UL 464 clause
39.1e)