3. Specifications

Output signal Pt100

Temperature range

Measuring range -50 ... +150 °C, -50 ... +250 °C

Measuring element

Pt100 (measuring current: 0.1 ... 1.0 mA) standard measuring resistor

Pt100 (measuring current: 0.1 ... 1.0 mA) face-sensitive measuring

resistor

1)

Connection method

3-wire

4-wire

Sensor tolerance value

2)

per DIN EN 60751

Class B

Class A

Class AA

Output signal 4 ... 20 mA

Temperature range

Measuring range -50 ... +150 °C, -50 ... +250 °C

3)

Measuring element

Pt100 (measuring current: 0.5 mA) standard measuring resistor

Pt100 (measuring current: 0.5 mA) face-sensitive measuring resis-

tor

1)

Connection method

3-wire

Sensor tolerance value

2) 4)

per DIN EN 60751

Class B

Class A

Class AA

Measuring span

minimum 20 K, maximum 300 K

Basic configuration

Measuring range -50 ... +150 °C, -50 ... +250 °C depending on the

selected temperature range, other measuring ranges are adjustable

Analogue output

4 ... 20 mA, 2-wire

Measuring deviation

per DIN EN 60770, 23 °C ±5 K

0.2 % (Transmitter)

4)

Linearisation

linear to temperature per DIN EN 60751

Linearisation error

±0.1 %

5)

Switch-on delay, electrical

< 10 ms

Signalling of sensor burnout

configurable: NAMUR downscale < 3.6 mA (typically 3 mA)

NAMUR upscale > 21.0 mA (typically 23 mA)

Sensor short-circuit

not configurable, generally NAMUR downscale < 3.6 mA (typically

3 mA)

Load R

A

R

A

≤ (U

B

- 10 V) / 0.023 A with R

A

in Ω and U

B

in V

Effect of load

± 0.05 % / 100 Ω

Power supply

DC 10 ... 35 V

Max. permissible residual ripple 10 % at 24 V / maximum 300 Ω Load

Power supply input

protected against reverse polarity

3. Specifications

Readings in % refer to the measuring span

For a correct determination of the overall measuring error, both sensor and transmitter measuring deviations have to

be considered.

1) The small design of the face-sensitive measuring resistors leads to reduced heat dissipation with short insertion lengths.

Available for temperature range -50…+150 °C in Classes A and B.

Face-sensitive measuring resistors are generally used for thermowell insertion lengths smaller than 11 mm.

2) For detailed specifications for Pt100 sensors, see Technical Information IN 00.17 at www.wika.com

3) The temperature transmitter should therefore be protected from temperatures over 85 °C

4) For measuring spans smaller than 50 K additional 0.1 K

5) ± 0.2 % for measuring ranges with a lower limit less than 0 °C