beautypg.com

Figure 8 figure 9, Figure 7a – DuraVent DuraPlus HTC User Manual

Page 10

background image

10

section, with the bead resting on the circular
opening in the plate (Fig 8). Slide the Collar
down on top of the Radiation Shield to
complete the Firestop Radiation Shield
installation.
For 6" diameter chimney, a Reduced
Clearance Firestop Radiation Shield is
available. This Firestop has the same
dimensions as the Reduced Clearance
Support Box, so it can fit between tight
framing members. Important: the 2"
minimum clearance to combustibles
must still be maintained for the rest of the
installation (other than the framing for
the Reduced Clearance Support Box and
Firestops), including the chase enclosure
between the Support Box and the Firestop.

7. Assemble Chimney Sections: Lower
the female end of the first Chimney Section
in the Support Box (Fig 9). It will twist-lock
clockwise onto the male end of the Support
Box. Turn Pipe Sections firmly clockwise 1/8
of a turn to lock them together. Sheet metal
screws are not required, but they may be
used to reinforce the connection, if desired.
Use only 1/2” (13 mm), or shorter, stainless
steel sheet metal screws. Do not penetrate
the inner liner of the chimney.

8. Install Attic Insulation Shield: In the attic
space, one of the following methods must be
used to prevent the chimney from contacting
attic insulation:
1. Use the Ceiling Support Box with Collar
2. Use Firestop Radiation Shield with Collar
3. Fully enclose the chimney through the attic
(maintain 2" minimum clearance).
DuraPlus HTC uses either a tall Cathedral
Ceiling Support Box with an Attic Insulation
Collar or a Firestop Radiation Shield with
its own Collar to act as an attic insulation
shield (Fig 10). If needed, the Attic Insulation
Collar can be trimmed to fit between framing
members, as long as it still covers the Support
Box or Firestop Radiation Shield. The Support
Box or the Firestop Radiation Shield must be

Figure 8

Figure 9

TWIST CHIMNEY

SECTION CLOCKWISE

TO LOCK INTO

SUPPORT BOx

Figure 7A

INSTALL RADIATION SHIELD

FROM ABOVE SO BEAD

RESTS ON FIRESTOP. ADjUST

ExTENSION SHIELD SO TOP

IS ABOVE LEVEL OF ATTIC

INSULATION. PUSH COLLAR

DOWN ONTO ExTENSION TUBE.

FRAMED OPENING

(SEE TABLE 2)

INSTALL

FIRESTOP

BELOW

FRAMING

WOOD

SCREWS

(4 REq)

MIN. 3"

(75MM)

BELOW

FINISHED

CEILING

SECURE

GUIDE

RAILS TO

SUPPORT

BOx WITH

SHEET

METAL

SCREWS