background image

IC0020: iCLASS

®

Module

Installation Directions

3. Drill a 3/8” hole for the door position switch (DPS) as required.

Note that the DPS may be positioned as desired, within the

limits of its 10” cable. If necessary (e.g. wood frames), drill a

channel from the DPS to the electric strike to accommodate

the 10” cable. Next drill a matching 3/8” hole in the door and

install the press-fit magnet so it will make contact with the DPS.

Wire Gauge Diagram

12VDC

100’ or less

24 Gauge

2

Distance In ft, Round Trip

100’ to 200’
200’ to 300’
300’ to 400’
400’ to 500’

22 Gauge
22 Gauge
22 Gauge
20 Gauge

24VDC

24 Gauge
24 Gauge
24 Gauge
22 Gauge
22 Gauge

© 2011 HES, Inc.

3078006.003 rev A

Non-surface mount for

electric strike installation

Surface mount

electric strike installation

Connect Components and Wiring

5. Select the appropriate 4-pin strike power pigtail tha matches system

power. For 12V AC/DC or 16V AC, the pigtail marked “12 VDC” should

be used. For 24V AC/DC, the pigtail marked “24 VDC should be used.

6. Verify that the wires running from the control panel are of adequate

wire gauge (see Wire Gauge Diagram below). Connect the wire leads of

the three pigtails provided (items 8, 9, & 11) to the control panel wiring

based on the wiring diagram on page 1 and the appropriate termination

at the control panel.

7. Mount the door position switch (DPS) into the frame. Route the cable

back to the electric strike and connect it to the 2 pin connector of item

13, adapter cable. Connect the 3 pin connector from the strike to the 3

pin connector of item 13. Connect the remaining 2 pin connector of

item 13 to the 2 pin connector of the iCLASS. The LBM & DPS are wired

in series--a ‘closed’ electrical circuit depicts a closed door and extended

latchbolt into the integrated electric strike.

8. Secure the reader/antenna mounting plate to the frame using the #6

sheet metal screws provided. Connect the 18” cable to the reader/

antenna, snap the reader/antenna to the reader/antenna mounting

plate and pull the 18” cable through to the iCLASS Module.

9. Attach all the 8, 4 and 2 pin connectors to the equivalent pigtail

connectors routed from the control panel. Dielectric grease can be

applied to the pigtail electrical terminals if used in a humid

environment.

10. Slide the iCLASS module through either the access slot or the electric

strike cutout depicted in the illustrations to the left.

11. Install the electric strike unit in the frame as specified in the specific

strike installation instructions.

Testing and Operation

12. When power is supplied, the LED will turn red, while the beeper beeps

3 times. This sequence indicates the micro-controller is operating

properly.

13. Present a iCLASS ID card to the reader/antenna. The LED will turn

green, while the beeper beeps once. This indicates that the card was

read successfully. Simultaneously, the keeper will click open. This

indicates that communication between the control panel and the

electric strike is operational.

Reorient or relocate the receiving antenna.

Increase the separation between the equipment and receiver.

Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

Consult the dealer or an experienced radio/TV technician for help

Warning: Changes or modification to this device not expressly approved by HES

®

, Inc., could void the user’s authority to operate the equipment.

NOTE: This equipment has been tested and found to comply within the limits for a class [B] digital device, pursuant to Part 15 of the FCC Rules. These

limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can

radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio or television

reception, which can be determined by turning the equipment off and on. The user is encouraged to try to correct the interference by one or more of the

following measures:

This class [B] digital apparatus meets all requirements of the Canadian Interference Causing Equipment Regulations.

Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference

received, including interference that may cause undesired operation. Cet appareillage numérique de la classe [B] répond à toutes les exigences de

l’inerférencé canadienne causant des réglements d’équipement. L’opération est sujette aux deux conditions suivantes: (1) ce dispositif peut ne pas causer

l’interférence nocive, et (2) ce dispositif doit accepter n’importe quelle interférence reçue, y compris l’interférence quipeut causer ’opération peu désirée.

Prepare Frame and Strike

1. Prepare door jamb per the Installation Instructions provided

with the electric strike.

2. On the outside side of the frame drill a 3/4” diameter hole for

reader/antenna install per the image below. The reader/

antenna may be positioned as desired, within the limits of

the 18” cable connected to the iCLASS Module.

1-5/16” [33]

5/8” [16]

3/4” [19]

DPS: 3/8” [10]

Cut

between

holes to

make this

slot

See 9400,9500/9600

installation instructions

for these wire hole locations