H. STEAM INFORMATION

It is your responsibility to have ALL steam plumbing connections made by a qualified professional to assure that

the installation is adequate and conforms with local and state regulations or codes.

IMPORTANT: Failure to comply with the requirements stipulated in this manual can result in

component failure which will VOID THE WARRANTY.

NOTE: The MLS-200 is manufactured with a pneumatic (piston) damper system which requires an

external supply of air (80 psi +/- 10 psi [5.51 bars +/- 0.68 bars]). See Steam Damper Air

System Connections Section H, item 3.

1. Steam Coil PH Level

The normal PH level for copper type steam coils must be maintained between a value of 8.5 to 9.5. For

steel type steam coils the PH level must be maintained between a value of 9.5 to 10.5. These limits are set

to limit the acid attack of the steam coils.

IMPORTANT: Coil failure due to improper PH level will VOID THE WARRANTY.

2. Steam Requirements - High Pressure

Inlet --------- 2-inch supply line connection

Return ------ 2-inch return line connection

3. Installation Instructions

To insure that an adequate supply of steam is provided, be sure that the steam supply and steam return lines

are sized and laid out as stipulated in this manual. Inadequate steam supply and steam return lines or

improper steam plumbing will result in poor performance and can cause component failure. Clean, dry,

regulated steam must be provided to the dryer.

IMPORTANT: Steam coil failure due to water hammer by wet steam will VOID THE WARRANTY.

a. The presence of the condensate in the steam supply will cause water hammer and subsequent heat

exchanger (steam coil) failure. The steam supply connection into the main supply line must be made

within a minimum 10-inch (25.4 cm) riser. This will prevent any condensate from draining towards the

dryer.

O

PERATING

S

TEAM

P

RESSURE

,

H

IGH

P

RESSURE

Maximum

125 psig

8.79 kg/sq cm

Minimum

100 psig

7.03. kg/sq cm

Heat Input (Normal Load)

27 Bhp

Consumption (Approximate)

800 lbs/hr

362 kg/hr

Shaded areas are in metric equivalents