IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is

affixed to the left side panel behind top/access control door. In the case of 208 VAC
or 240 VAC, the supply voltage must match the electric service specifications of the
data label exactly.

WARNING: 208 VAC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer

components due to improper voltage connections will automatically VOID THE
WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time without notice or

obligation.

IMPORTANT: 380, 400, and 416 Volt dryers are built 4-wire only. Customer must contact the

factory to special order 3-wire systems.

ADE-115ES (72 Kw Electric Oven) Reversing, 3ø M otor

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

NOTES: A. When fuses are used they must be dual element, time delay, current limiting, class RK1or RK5 ONLY. Calculate/determine

correct fuse value, by applying either local and/or National Electrical Codes to listed appliance amp draw data.

B. Circuit breakers are thermal-magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to

appliance amp draw rating and type of breaker used.

C. Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.

OVEN SIZE

(Kw)

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

MINIMUM
WIRE SIZE

FUSING

CIRCUIT

BREAKER

60 Hz

50 Hz

Dual Element

Time Delay

72

208

3

214

--

*

300

300

72

240

3

188

190

*

250

250

72

380

4**

--

118

*

150

150

72

400

4**

--

112

*

150

150

72

416

4**

--

108

*

150

150

72

460

3

98

--

*

125

125

72

480

3

94

--

*

125

125

72

575

3

78

--

*

100

110

*AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.

(Motor lead wire is recommended.)

**3-wire available.