All ACI/34 and ACI/334 semiconductor sensors are polarity sensitive but non-position sensitive. The
ACI/34 Duct sensor is supplied with a 3-Pole terminal block while the ACI/LM334 has a 2-Pole terminal
block for all wiring connections. ACI recommends the use of 18 to 22 AWG twisted pair or shielded
cable for all sensor installations.
Sensor reads supply voltage
Sensor or wires are shorted together
Sensor reads 0 mA or 0 VDC
Sensor or wires are open
Erratic readings
Bad wire connections / Condensation on board
+ -
LM334
Sensor
Sensor Output to
Controller in uA
+5 to 24 VDC Power
Supply
+ s -
LM34
Sensor
Common or Ground of
Controller or power
Supply
+15 VDC Power
Supply
Sensor Output to
Controller in mV
LM334
LM34