Automation Components Separate Input w/RJ12 Phone Jack User Manual
Ac i, Installation and operation instructions, Separate input w/rj12 phone jack
Installation and Operation Instructions
Separate Input w/RJ12 Phone Jack
2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562
PH: (608) 831-2585 FAX: (608) 831-7407
II-9
A
C
I
utomation
omponents
nc.
READ THESE INSTRUCTIONS BEFORE YOU BEGIN INSTALLATION
All ACI thermistors and RTD temperature sensors are both non-polarity and non-position sensitive. All thermistor type
room units are supplied with a two-pole terminal block and all RTD’s can be supplied with either a two or three-pole
terminal block.
All of the following units are available with corresponding terminal blocks for all connections: Rooms with Setpoint (RS),
Rooms with Override (RO), Rooms with Setpoint and Override (RSO), and Rooms with Setpoint, Override, and RJ12
Communication Jack (RSO RJ12).
**Note: All Room with Override (RO) and Room with Setpoint and Override (RSO) sensors are shipped with the
Override in Parallel with the sensor unless specified otherwise. If a Separate Input or Tenant Override is
Needed, see Figure #1 for the Override Options Jumper Settings.
i
All other configurations are supplied with 22 gauge lead wires and can be hooked up with any crimp style or wire nut wire
connectors. ACI recommends the use of 18 to 22 AWG twisted pair wires or shielded cable for all sensor installations.
n
TROUBLESHOOTING
Sensor reads 0 ohms or very low
Sensor or wires are shorted together
Sensor reads infinity or very high
Sensor or wires are open
Erratic readings
Bad wire connections - Condensation or Moisture problem
n
WIRING DIAGRAMS
J2
Short Sensor
Separate Input
SW1
Gnd + - S ET O / R
1 2 3 4 5 6
6
1
6 Pin RJ12
Communication Jack
Thermistor and Override
Output to Controller
Thermistor and Override
Output to Controller
Setpoint Output to Controller
Setpoint Output to Controller
Tenant Override (Dry Contact) Output
to Controller
(Separate Input Only)
Tenant Override (Dry Contact) Output
to Controller
(Separate Input Only)
Terminals for RJ12 Communications
J3
Membrane
Wire Access Hole
“After Hours” Normally-Open
Override Switch
Override Options Jumper Settings (J3)
Short Sensor
Short Sensor
Separate Input
Override Shorts
Separate Input
Sensor
(Dry Contact Closure
)
Figure #1
Separate Input
.
** NOTE: (J2) is only used for Connection of the Membrane Switch.
*** NOTE: When wanting to use a Single Common for all (3) of the Outputs on a Separate Input Sensor,
connect one wire in series with one of the Sensor, Setpoint, and Override Terminals. These three
terminal may then be tied to the common of the controller with one wire, while the other three
terminals would need to be connected to the proper Sensor Inputs of your controller.
Multi6 Rev 7
c