Efbc-4l fluorescent dimming ballast controller, Page 2 of 2 – Pathway EFBC-4L Configuration User Manual
Page 2

B5<1I<5F5 This rotary switch sets the low-end cutoff point for all 4 4=H144B5CCC5<53D9?>CG"$ Three rotary switches select the DMX start address for =?45C5<53D49@CG9D38CG% S1-S4 CONTROL BYPASS S5 ANALOG INPUT ENABLE When in “ON” position, all 4 analog inputs are enabled. Each switch turns the associated output on full when in S6 SCALED HOLD ENABLE “ON” selects fluorescent dimming curve. “OFF” selects S7 STATUS OUTPUT ENABLE When “ON” will maintain the last active levels for 5 min. S8 CONTACT CLOSURE POLARITY Sets the polarity of the contact closure input. “ON” se- <549>4931D?BC Two LEDs are used to indicate processor/power supply RUN Glowing steadily indicates power supply and RxD Glowing steadily indicates data signal received; FL1 - FL4 when illuminated indicate a wiring fault on the OP1-OP4 indicate ballast control (drive) level. The LEDs EFBC-4L FLUORESCENT DIMMING BALLAST CONTROLLER Page 2 of 2 >?D5C GENERAL supply. INPUTS OUTPUTS CAPACITY MOUNTING J3 SCREW TIGHTENING TORQUE 5<53DB931 Control Input : 120/240/277 V, 60 Hz, 0.15A 09/00 rev8 ver3.1 3ULQWHG LQ &DQDGD www.gray-interfaces.com *5$< Gray Interfaces, 480C - 36 Avenue S.E.,
switched hot relays in steps of 1 to 10 percent. Position
"0" selects 10%.
the card's four channels. The switches are set as hun-
dreds, tens and units. Address 000 and 001 both select
DMX address 1.
the “ON” position.
linear (standard) curve.
after loss of DMX control signal
lects normally open, “OFF” selects normally closed.
status and data receive detection.
processor OK; off indicates no power, and flash-
ing indicates defective processor hardware.
off indicates no signal present. Note that an ad-
dress selection out of the DMX signal range will
turn off the LED.
"dimmed hot" line(s). The indicated output(s) should be
disconnected, the fault cleared, and then reconnected.
increase in brightness in proportion to the signal level.
The interface is designed to directly control Lutron Hi-
Lume FDB & ECO series electronic fluorescent dimming
ballasts from industry standard low voltage lighting con-
trol signals. Four separate channels of control are pro-
vided on each interface card. NOTE: When using ECO
series ballasts, all circuits controlled by the same
interface card must be connected to the same phase
as the card power
Each channel of dimming is capable of individual control
from 0-10VDC (analog) and DMX512 (digital) control
sources. Where both sources of control are connected
and enabled, they will function in a highest level takes
precedence (pile on) mode.
Each output consists of a ballast control (dimmed hot)
lead and a ballast power (switched hot) lead. Dimmed
hot outputs are internally fused to protect the interface
card against fault currents and miswiring. Each hot out-
put incorporates a relay contact which opens when the
control signal level falls below the level preselected by
"SW1", shutting off power to the ballast(s).
Each output is capable of controlling up to an average of
25 120V or 50 277V ballasts per channel, depending on
the ballast type.
The interface should be mounted on minimum 0.5 inch
high #6-32 standoffs.
Maximum Torque: 0.5 Nm / 4.5 lb-in
Fuse: GMA 200mA
Switched Outputs: 120/240/277 V, 60Hz, 20A
Fuse: Protected by external circuit breaker
Dimmed Outputs: 120/240/277 V, 60Hz, .15A
Fuse: GDC2A
Calgary, AB, T2G 1W4 Canada