Additional Installation Tips

6.2 Ethernet Connection in the Panel

1

2

3

4

5

1-1
2-2
3-3

8-8

RJ45

RJ45

RJ45

RJ45

RJ45

RJ45

RJ45

RJ45

Industrial Ethernet

Operator panel

Operator panel

Operator panel

Operator panel

Shielded

Short and
unshielded

0.1 uF
250 V

5351

In some industrial units for Ethernet, the RJ45 contact’s shield is connected to the
chassis via a capacitor, see 1 in drawing above.
The operator panel’s Ethernet shield is directly connected to the chassis, see 2 in
drawing above.
1. Check whether the other Ethernet unit has its shield directly grounded or

grounded via a capacitor.

Note:
In many cases, connecting the shielded Ethernet cabling to the chassis at both ends is
inappropriate. Hum or grounding loops can occur. Unshielded cabling may even result
in fewer communication errors.

A good solution may be to use a shielded Ethernet cable, but to connect the shield
at one end only.
One option is to break the shield, see 3 in drawing above.
A more elegant method is to expand the shielded Ethernet cabling with a piece of
unshielded Ethernet cable, see 4 in drawing above.
You can ground the shield via an external 0.1 uF/250 V plastic capacitor, see 5 in
drawing above. This will connect the HF transients to the ground.