IMPORTANT: Minimum duct size for dryer is 10-inches (25.40 cm) round duct. Duct size must not

be reduced anywhere downstream of dryer.

IMPORTANT: It is recommended that exhaust or booster fans not be used in the exhaust ductwork

system.

NOTE: As per the National Fuel Gas Code, “Exhaust ducts for type 2 clothes dryers shall be

constructed of sheet metal or other noncombustible material. Such ducts shall be equivalent in
strength and corrosion resistance to ducts made of galvanized sheet steel not less than
26 gauge (0.0195-inches [0.50 mm]) thick.”

2. Venting Layout

a. Single Dryer Venting

When single dryer venting is used, for horizontal or vertical venting the minimum duct size is 10-inches
(25.40 cm) in diameter and the ductwork from the dryer to the outside exhaust outlet must not exceed
a distance and the number of elbows (including both connection to dryer and outside protection shown
in the illustration below).

IMPORTANT: Exhaust back pressure measured by a manometer at the dryer exhaust duct area must

be no less than 0 and must not exceed 0.3 inches (0.74 mb) of water column
(W.C.).

CAUTION: IMPROPERLY SIZED OR INSTALLED EXHAUST DUCTWORK CAN

CREATE A POTENTIAL FIRE HAZARD.