1. Specifications

3-2. Air-Discharge Chamber for Top Discharge

Be sure to install an air discharge chamber in the
field when:

it is difficult to keep a space of min. 20" between

the air discharge outlet and an obstacle.

the air discharge outlet is facing a sidewalk and

discharged hot air may bother passers-by.
Refer to Fig. 1-7.

3-3. Installing the Unit in Heavy Snow Areas

In locations with strong wind, snow-proof ducting
should be fitted and direct exposure to the wind
should be avoided as much as possible.

Countermeasures against snow and wind

In regions with snow and strong wind, the following
problems may occur when the outdoor unit is not provided
with a platform and snow-proof ducting:

a)

unit may occur.

b)

c)

d)

The outdoor fan may not run and damage to the

There may be no air flow.

The tubing may freeze and burst.

The condenser pressure may drop because of
strong wind, and the indoor unit may freeze.

3-4. Precautions for Installation in Heavy Snow Areas

(1)

depth. (Fig. 1-8)

(2)

used for the platform, and the platform should be
installed beneath the air intake side of outdoor unit.

(3)

must be secured with anchor bolts.

(4)

The platform should be higher than the max. snow

The 2 anchoring feet of the outdoor unit should be

The platform foundation must be firm and the unit

In case of installation on a roof subject to strong
wind, countermeasures must be taken to prevent
the unit from being blown over.

Fig. 1-7

Fig. 1-8

Fig. 1-9

In regions with significant snowfall, the outdoor unit should
be provided with a platform and snow-proof duct.

Air discharge

Air discharge

Without snow-
proof ducting
(Low platform)

With snow-
proof ducting
(High platform)

Outdoor

Duct

Air

Unit