Specifi cations

Single Split Outdoor Unit

Model Name

U-50PE1E5

U-60PE1E5

U-71PE1E5

U-100PE1E5

U-125PE1E5

U-140PE1E5

Power source

220/230/240 V∼ 50 Hz

Cooling capacity

kW

5.0 6.0 7.1 10.0 12.5 14.0

BTU/h

17,100

20,500

24,200

34,100

42,700

47,800

Heating capacity

kW

5.6 7.0 8.0 11.2 14.0 16.0

BTU/h

19,100

23,900

27,300

38,200

47,800

54,600

Sound pressure

level (C/H)

dB(A)

46 / 50

48 / 50

48 / 50

52 / 52

53 / 53

54 / 55

Sound power level

(C/H)

dB(A)

65 / 69

65 / 67

65 / 67

69 / 69

70 / 70

71 / 71

Unit dimensions

(H×W×D)

mm

569Ч790Ч285

996Ч940Ч340

996Ч940Ч340

1,416Ч940Ч340 1,416Ч940Ч340 1,416Ч940Ч340

Net weight

kg

42 68 69 98 98 98

Model Name

U-71PE1E8

U-100PE1E8

U-125PE1E8

U-140PE1E8

Power source

380/400/415 V 3N∼ 50 Hz

Cooling capacity

kW

7.1 10.0 12.5 14.0

BTU/h

24,200

34,100

42,700

47,800

Heating capacity

kW

8.0 11.2 14.0 16.0

BTU/h

27,300

38,200

47,800

54,600

Sound pressure

level (C/H)

dB(A)

48 / 50

52 / 52

53 / 53

54 / 55

Sound power level

(C/H)

dB(A)

65 / 67

69 / 69

70 / 70

71 / 71

Unit dimensions

(H×W×D)

mm

996Ч940Ч340

1,416Ч940Ч340 1,416Ч940Ч340 1,416Ч940Ч340

Net weight

kg

71 98 98 98

Model Name

U-60PEY1E5

U-71PEY1E5

U-100PEY1E5 U-125PEY1E5

Power source

220/230/240 V∼ 50 Hz

Cooling capacity

kW

6.0 7.1 10.0 12.5

BTU/h

20,500

24,200

34,100

42,700

Heating capacity

kW

6.0 7.1 10.0 12.5

BTU/h

20,500

24,200

34,100

42,700

Sound pressure

level (C/H)

dB(A)

46 / 50

50 / 52

54 / 54

56 / 56

Sound power level

(C/H)

dB(A)

65 / 69

70 / 70

70 / 70

73 / 73

Unit dimensions

(H×W×D)

mm

569Ч790Ч285

569Ч790Ч285

996Ч940Ч340

996Ч940Ч340

Net weight

kg

42 42 73 85