beautypg.com

E. exhaust requirements – American Dryer Corp. MLG32PDB User Manual

Page 16

background image

12

Maytag Co.

113062 - 16

E. EXHAUST REQUIREMENTS

Exhaust ductwork should be designed and installed by a qualified professional. Improperly sized ductwork will
create excessive back pressure, which results in slow drying, increased use of energy, overheating of the dryer,
and shutdown of the burner by the airflow (sail) switches, burner hi-limits, or basket (tumbler) hi-heat thermostats.
The dryer must be installed with a proper exhaust duct connection to the outside.

CAUTION: This dryer produces combustible lint and must be exhausted to the outdoors.

CAUTION: IMPROPERLY SIZED OR INSTALLED EXHAUST DUCTWORK CAN

CREATE A POTENTIAL FIRE HAZARD.

The exhaust ductwork should be laid out in such a way that the ductwork travels as directly as possible to the
outdoors with as few turns as possible. When single dryer venting is used, the ductwork from the dryer to the
outside exhaust outlet must not exceed 10 feet. In the case of multiple (common) dryer venting, the distance
from the last dryer to the outside exhaust outlet must not exceed 20 feet. The shape of the exhaust ductwork
is not critical so long as the minimum cross-sectional area is provided.

1. Single Dryer Venting

When possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust ductwork
should be laid out in such a way that the ductwork travels as directly as possible to the outdoors with as
few turns as possible. It is suggested that the use of 90° turns in ducting be avoided; use 30° or 45° angles
instead. The shape of the exhaust ductwork is not critical so long as the minimum cross-sectional area is
provided.

IMPORTANT: Exhaust back pressure measured by a manometer at the dryer’s exhaust duct area

must be no less than 0 and must not exceed 0.3 inches of water column (W.C.)
when both baskets (tumblers) are operating.

It is suggested that the ductwork from each dryer not exceed 10 feet with no more than two (2) elbows. If
the ductwork exceeds 10 feet or has numerous elbows, the cross-sectional area of the ductwork must be
increased in proportion to length or number of elbows in it.

IMPORTANT: For extended ductwork runs, the cross-sectional area of the ductwork can only be

increased to an extent. Maximum proportional ductwork runs cannot exceed 10 feet
more than the original limitations of 10 feet with two (2) elbows. When the ductwork
approaches the maximum limits as noted in this manual, a professional heating,
ventilation, and air-conditioning (HVAC) firm should be consulted for proper venting
information.

The ductwork should be smooth inside with no projections from sheet metal screws or other obstructions,
which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be
connected. ALL ductwork joints must be taped to prevent moisture and lint from escaping into the
building. Also, inspection doors should be installed at strategic points in the exhaust ductwork for periodic
inspection and cleaning.

IMPORTANT: It is recommended that exhaust or booster fans not be used in the exhaust ductwork

system.