beautypg.com

Appendix – absorption distance calculation – Aprilaire 1150 User Manual

Page 38

background image

APPENDIX – ABSORPTION DISTANCE CALCULATION

Step 1: Enter the Design Conditions

Percentage of Outdoor Air

OA:

Indoor Air Temperature

T

Indoor

:

Setpoint Indoor RH (for the leaving air)

RH

Leaving

:


Step 2:
Find the ‘Moisture Content Factor’ for the leaving air (M

Leaving

)

In

Table 7, find the intersection of T

Indoor

and

RH

Leaving

. The intersection of those

two points is the ‘Moisture Content Factor’ for the leaving air.

M

Leaving

:


Step 3:
Find the ‘Moisture Content Factor’ of the entering air (M

Entering

)

Use the following equation to calculate the moisture content of the entering air:

M

Entering

= M

Leaving

x (1 -

OA/100)

Note: this step assumes that the outdoor air being brought into the system will
contribute an insignificant amount of moisture relative to what’s being added by
the humidifier.

M

Entering

:

For example: if Outdoor Air percentage is 20% and the M

Leaving

factor is 2.4, the calculation would be:

M

Entering

= 2.4 x (1 - 20/100) = 1.92


Step 4:
Find the RH for the entering air

In

Table 7, find the row that corresponds to the temperature T

Indoor

. Then, slide

across this row and find the value closest to

M

Entering

, which was calculated in Step 3.

Finally, slide up this column to determine the RH for the

entering air.

RH

Entering

:


Step 5:
Find the Absorption Distance

Using the Absorption Chart,

Figure 33, draw a vertical line up from the intersection

of

RH

Entering

along the bottom horizontal axis to the intersection of the diagonal line

corresponding to

RH

Leaving

. From this point draw a line horizontally to the intersection

of the duct height. This is the minimum required absorption distance for the given duct
height and the above Design Conditions.

Note: ‘duct height’ assumes a horizontal flow system. For vertical drop systems, duct
height should be considered as the duct dimension perpendicular to the distribution tube.

Absorption Distance:

Example: The design conditions of 40% outdoor air, 72°F indoor air temperature, and an indoor RH setpoint of 50% would
require an absorption distance of 20” in a system with a duct height of 18”. (

M

Leaving

would be 3.68,

M

Entering

would be 2.20,

and

RH

Entering

would be 30%)

38

This manual is related to the following products: