Problem

Possible Cause

Action

The On/Off light on

the display panel is

blinking slowly (one

blink per second)

Mineral buildup or

oxidation on probe rods

• Remove probe assembly and clean probe rods; reset power to clear warning.

Deterioration of probe rod

assembly

• Replace probe rod assembly.

The On/Off light on

the display panel is

blinking rapidly (10

blinks per second)

(illogical probe fault)

Probe is wired incorrectly

• Verify wiring; see wiring diagram.

• Verify that probe wires are routed separately from high voltage wires to avoid interference.

• Verify the green and yellow ground wire is connected to the subpanel and to the C terminal.

Deterioration of probe rod

assembly

• Replace probe rod assembly.

Chamber water is foaming.

• Clean chamber.

No remote fault

indication (drain fault,

fill fault, illogical

probe fault)

Note: This is an

optional connection

Field wiring not installed

• Provide field wiring to a remote fault indicator from NO, O, NC control terminal block.

Remote fault relay is not

switching.

• Check relay continuity NO, O, NC control terminal block for contact closure.

Field-supplied remote fault

indicator lamp is burned out.

• Check if lamp by others is burned out; replace if needed.

System fan/blower

doesn’t operate

System fan/blower power

is off

• Turn power supply on.

System fan/blower is not

wired to internal controller

board

• Check wiring diagrams on pages 9 and 10 for wiring to NO, O, and NC terminals.

Internal controller board is

configured for remote fault

indication

• Slide switch S2 position 9 must be in ‘off’ position. See page 11 for more information.

Humidifier does not

energize; chamber

does not heat up

Nonexistent supply voltage

to humidifier

• Check main line fuse.

• Check main line safety switch.

• Verify contactor electrical plug is fully engaged.

Nonexistent control voltage • Check for proper supply voltage per wiring diagram.

• Verify proper wiring of multi-tap transformer.

• Verify transformer electrical plug is fully engaged.

• Check for control circuit voltage, 24 VAC. If voltage is not present at H and C, check transformer

circuit breaker.

• Reset if needed by pressing On/Off switch on display panel.

• Reset manual over-temperature switch located above heater on humidifier cover.

Humidifier

over-temperature

thermostat is open.

• Reset manual switch located above heater on humidifier cover.

• Verify contactor and transformer electrical plugs are fully engaged.

Non-resettable over-

temperature thermostats (in

power lines to heaters) are

open. (Model 1160 only.)

• Replace non-resettable thermostats.

• Check all components for over-temperature damage.

• Determine cause of dry fire by checking for a frozen contactor or a probe assembly malfunction

and remedy before restarting humidifier.

Reduced or no output

(even though water

level is correct)

Malfunctioning control

system

• Check if auxiliary limit controls are not allowing system to operate, e.g., high humidity limit

switch, airflow proving switch, etc.) Reset, replace, or calibrate as needed.

• Check if the heater over-temperature thermostat has tripped. Reset if necessary.

• Check if the non-resettable over-temperature thermostats have tripped. Replace if necessary.

• Check fuse in power circuit. If open, replace fuse with equal fuse.

Heater malfunctioning

• Verify that contactor and transformer electrical plugs are fully engaged.

• Verify that proper voltage is being applied to heaters.

• Check heater amperage.

• If heater power device is not functioning, replace.

33