2. Electrical Service Specifications

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is

affixed to the left side panel area behind the top control (access) door (refer to the
illustration on page 9). In the case of 208 VAC or 240 VAC, the supply voltage
must match the electric service specifications of the data label exactly.

WARNING: 208 VAC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer

components due to improper voltage connections will automatically VOID THE
WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time without notice or

obligation.

ML-122 (Gas and Steam Only)

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.

C.

208 VAC AND 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.

When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5
ONLY. Calculate/determine correct fuse value, by applying either local and/or National Electrical

Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY . For others, calculate/

verify correct breaker size according to appliance amp draw rating and type of breaker used.

Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

MINIMUM

WIRE SIZE

FUSING

CIRCUIT

BREAKER

Dual Element

Time Delay

60 Hz

50 Hz

208

3/4

12.6

--

*

20

25

240

3

11

12.5

*

20

20

380-400

3/4

--

5.5

*

15

15

416

3/4

--

5.6

*

15

15

460/480

3/4

8.6

--

*

15

15

* AWG Stranded Wire Type...size wire as per National Electrical Code or local codes.