* 380 volt dryers are built 4-wire only. Customer must contact factory to special order 3-wire systems.

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is

affixed to the left side panel/wall area behind the control door. In the case of 208
VAC or 240 VAC, the supply voltage must match the electric service specifications of
the data label exactly.

WARNING: 208 VAC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer

components due to improper voltage connections will automatically VOID THE
WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time without notice or

obligation.

051303

ADE-120 III (72 kW Electric)

Reversing, 3ø

ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

IMPORTANT:

NOTES: A.

B.

C.

208 VAC and 240 VAC ARE NOT THE SAME. When ordering,

specify exact voltage.

When fuses are used they must be dual element, time delay,

current limiting, class RK1 or RK5 ONLY. Calculate/determine

correct fuse value, by applying either local or National Electrical

Codes to listed appliance amp draw data.

Circuit breakers are thermal-magnetic (industrial) type ONLY.

For others, calculate/verify correct breaker size according to

appliance amp draw rating and type of breaker used.

Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

OVEN SIZE

(kW)

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

60 Hz

50 Hz

72

208

3

214

---

72

240

3

188

191

72

380

4*

---

118

72

460

3

98

---