Electrical service specifications (per dryer) – American Dryer Corp. Extended Side Panels AD-120ES III User Manual
Page 28

24
* 380 volt dryers are built 4-wire only. Customer must contact factory to special order 3-wire systems.
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the left side panel/wall area behind the control door. In the case of 208
VAC or 240 VAC, the supply voltage must match the electric service specifications of
the data label exactly.
WARNING: 208 VAC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or
obligation.
051303
ADE-120 III (72 kW Electric)
Reversing, 3ø
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES: A.
B.
C.
208 VAC and 240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay,
current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local or National Electrical
Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY.
For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
OVEN SIZE
(kW)
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
60 Hz
50 Hz
72
208
3ш
3
214
---
72
240
3ш
3
188
191
72
380
3ш
4*
---
118
72
460
3ш
3
98
---