Storage

Storage Conditions

Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS
for at least two hours. Remove any accessories in the accessory slot and disconnect any cables connected to the computer
interface port to avoid unnecessarily draining the battery.

Extended storage

At -15 to +30

°

C (+5 to +86

°

F), charge the UPS’s battery every six months.

At +30 to +45

°

C (+86 to +113

°

F), charge the UPS’s battery every three months.

User Configuration Items

Note: Setting these items requires optional software or hardware.

Function

Factory

Default

User Selectable

Choices

Description

Automatic Self-Test

Every 14
days (336
hours)

Every 7 days (168
hours), On Startup
Only, No Self-Test

Sets the interval at which the UPS will
execute a self-test.

UPS ID

UPS_IDEN

Up to eight characters
to define the UPS.

Use this field to uniquely identify the UPS
for network management purposes.

Date of Last Battery

Manufacture

Date of Battery

Reset this date on battery replacement.

Minimum Capacity Before
Return from Shutdown

0 percent

15, 50, 90 percent

The UPS will charge its batteries to the
specified percentage before return from a
shutdown.

Sensitivity

Normal

Reduced, Low

Set lower than normal sensitivity to avoid
lowered battery capacity and service life in
situations where the load can tolerate minor
power disturbances.

Duration of Low Battery
Warning

2 minutes

5, 7, 10 minutes

Sets the time before shutdown at which the
UPS issues a low battery warning. Set
higher than the default only if the OS needs
the time for graceful shutdown.

Alarm Delay After Line
Fail

5 second
delay

30 second delay, At
Low Battery
C

di i

Al

To avoid alarms for minor power glitches,
set the alarm delay.

Shutdown Delay

20 seconds

180, 300, 600 seconds

Sets the interval between when the UPS
receives a shutdown command and when
shutdown occurs.

Synchronized Turn-on
Delay

0 seconds

60, 180, 300 seconds

To avoid branch circuit overload, the UPS
will wait the specified time after the return
of utility power before turn-on.

High Transfer Point

200/208 Vac
230 Vac

229
253

224, 234, 239
264, 271, 280

To avoid unnecessary battery usage, set the
High Transfer Point higher if the utility
voltage is chronically high and the load is
known to work well under this condition.

Low Transfer Point

200/208 Vac
230 Vac

177
196

168, 172, 182
188, 204, 208

Set the Low Transfer Point lower if the
utility voltage is chronically low and the
load can tolerate this condition.